Kenmore KWX - 6V, KWX - 9V Check Gassupp, Connecting The Gas Piping, Checking The Gas Piping

Models: KWX - 7V KWX - 4V KWX - 9V KWX - 3V KWX - 5V KWX - 8V KWX - 6V

1 36
Download 36 pages 18.42 Kb
Page 10
Image 10
CHECK GASSUPP_

CHECK GASSUPP_

The gas pipe to your boiler must be the correct size for the length of the run and for the total Btu per hour input of all gas utilization equipment connected to it. See Fig. 12 for the proper size. Be sure your gas line complies with local codes and gas company requirements.

The boiler and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of I/2psig (3.5 kPa).

The boiler must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/zpsig (3.5 kPa).

CONNECTING THE GAS PIPING

Refer to Fig. 13 for the general layout at the boiler. It shows the basic fittings you will need. The gas line enters the boiler from the right side.

The following rules apply:

1.Use only those piping materials and joining methods listed as acceptable by the authority having jurisdiction,

or in the absence of such requirements, by the National Fuel Gas Code, ANSI Z223.1-1atest revision.

2.Use pipe joint compound suitable for LP gas on male threads only

3.Use ground joint unions.

4.Install a sediment trap upstream of gas controls.

5.Use two pLpe wrenches when making the connection to the gas valve to keep it from turning.

6.Install a manual shut-off valve in vertical pipe about 5 feet above floor.

7 Tighten all joints securely

CHECKING THE GAS PIPING

Upon completion of piping, check immediately for gas leaks Open the manual shut-off valve. Test for leaks by applying

soap suds (or a liquid detergent) to each joint. Bubbles forming indicate a leak CORRECT EVEN THE SMALLEST LEAK AT ONCE

WARNING

Never use a match or open flame to test for leaks.

NATURAL GAS

Pipe Capacity - BTU per Hour Input

Length ofIncludes Fittings Pipe - Ft.

V2"3/4"1"11/4"

2092,000 190,000 350,000 625,000

4063,000 130,000 245,000 445,000

6050,000 105,000 195,000 365,000

The length of pipe of tubing should be measured from the gas meter

10

Page 10
Image 10
Kenmore KWX - 6V, KWX - 9V, KWX - 8V, KWX - 3V, KWX - 4V Check Gassupp, Connecting The Gas Piping, Checking The Gas Piping