Resetting the FlexStat

Types of Reset

If the FlexStat is not operating correctly or if a low limit alarm has occurred, the FlexStat should be reset (reinitialized). Any reset interrupts normal op- eration, and three types of reset exist:

A warm start is generally the least disruptive op- tion (restarting normal operation the quickest).

If problems still persist, try a cold start. (This should also be used after a new Control Basic program is loaded and compiled.)

If problems still persist (or major changes in a firmware update have taken place) restoring fac- tory defaults (and reconfiguring and reprogram- ming the FlexStat) may be required.

Warm and Cold Starts

CAUTION

During a restart, the analog outputs go to zero, and relays go to their normally open state. A re- start is a process that lasts around ten seconds, and it may result in several changes of state

Restarts the controller’s Control Basic programs.

Leaves configuration and programming intact.

NOTE: Menu changes may take up to about two minutes to write to nonvolatile Flash memory. If power to the FlexStat is lost during this time, changes may be lost.

Restarting the FlexStat from its menu, TotalControl, or BACstage are the recommended methods.

NOTE: When power is restored after an outage, the FlexStat will attempt to do a warm start as long as the values in RAM are retained (up to about four hours). If the the RAM checksum test fails, a cold start will be done instead. (In custom Control Basic programming, using the POWERLOSS command may be desirable

to determine start-up conditions and to take appropriate actions—see the Help system in TotalControl or BACstage for more information.)

for an output, turning equipment off and on abruptly. Before resetting the FlexStat, manually override equipment as needed. If a large fan

is controlled by the FlexStat, for example, set a minimum off time. See Fan Setup on page 5 (built-in, selectable applications with compres- sors have a default programmed minimum off time of 300 seconds).

ADVANCED APPLICATION

CB PROGRAMS

COMMUNICATION DATE/TIME DEVICE

LIMITS SECURITY

DEVICE

INSTANCE: 1

NAME: FlexStat_101

LOCATION: KMC Controls

RESTART: WARM START

RESTORE FACTORY: NO

A warm start does the following in the FlexStat:

(After zeroing out objects during the restart process) restores present values of objects to their last values before the restart (until they are updated by the FlexStat’s programs).

Restarts the controller’s Control Basic programs.

Leaves configuration and programming intact.

CAUTION

If the checksum test in RAM fails during a warm start, a cold start is performed instead.

A cold start does the following in the FlexStat:

(After zeroing out objects during the restart process) returns all object values to their relin- quished defaults (until they are updated by the FlexStat’s programs).

To perform a WARM start, do one of the following:

From the FlexStat menu, select Advanced > De- vice > Restart > Warm Start.

From TotalControl or BACstage, select Reinitial- ize Device > Warm Start.

Momentarily remove power to the FlexStat.

To perform a COLD start, do one of the following:

From the FlexStat menu, select Advanced > De- vice > Restart > Cold Start.

From TotalControl or BACstage, select Reinitial- ize Device > Cold Start.

BAC-10000 Series

14

Operation Guide, Rev. J

Page 14
Image 14
KMC BAC-10000 manual Resetting the FlexStat, Types of Reset, Warm and Cold Starts

BAC-10000 specifications

The KMC BAC-10000 is a cutting-edge building automation controller designed to offer exceptional performance in monitoring and controlling HVAC systems, lighting, and various other building systems. This advanced controller is engineered to enhance energy efficiency, improve occupant comfort, and provide streamlined building management capabilities.

One of the main features of the KMC BAC-10000 is its versatility. It supports a wide variety of communication protocols, including BACnet, Modbus, and LonWorks. This multi-protocol capability allows for seamless integration with existing building systems, ensuring that users can easily incorporate the BAC-10000 into their building management setup without the need for additional hardware or extensive modification.

The controller is equipped with an intuitive user interface that simplifies the management of building systems. It includes a graphical display that provides real-time data, enabling operators to monitor system performance, adjust settings, and troubleshoot issues with ease. This user-friendly design promotes efficient operation and reduces the learning curve for new users.

In terms of technical specifications, the BAC-10000 boasts a powerful microprocessor and an extensive range of I/O points, allowing it to handle large and complex building automation tasks. With support for both digital and analog inputs and outputs, users can customize their setup to meet specific operational requirements.

Another standout feature of the KMC BAC-10000 is its advanced data logging capabilities. The controller can record historical data for various parameters, which can be crucial for performance analysis and optimization. This functionality enables facility managers to identify patterns, predict maintenance needs, and ultimately enhance the overall efficiency of their systems.

Security is also a priority with the BAC-10000, as it includes multiple layers of security protocols to protect against unauthorized access and tampering. This ensures that sensitive building management data remains safe and that users can operate the controller confidently.

In conclusion, the KMC BAC-10000 is a robust and flexible building automation controller that offers extensive features and technologies for effective building management. Its multi-protocol support, user-friendly interface, advanced data logging, and emphasis on security make it a top choice for modern building automation needs. By choosing the BAC-10000, facility managers can optimize energy usage, improve occupant comfort, and streamline operations within their buildings.