| INSTALLATION |
| 14 |
| |||
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| TABLE A – TERMINAL DESCRIPTIONS (continued) |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| TERMINAL | FUNCTION | FUNCTION |
|
|
|
|
|
|
| LABELS | (HEAT PUMP MODE) | COMMENTS |
|
| |
|
|
|
| E | Emergency heating | DO NOT CONNECT | Activates Emergency heating ONLY when the System Switch is in |
|
|
|
|
|
|
|
|
| Emergency (em) Mode. (Ignored on |
|
|
|
|
|
| O | Reversing valve | Cooling damper | Activates reversing valve or damper in COOL mode. |
|
|
|
|
|
|
| (cooling mode) |
| ALWAYS ON in COOL MODE. |
|
|
|
|
|
| B | Reversing valve | Heating damper | Activates reversing valve or damper in HEAT mode. |
|
|
|
|
|
|
| (heating mode) |
| ALWAYS ON in HEAT MODE. |
|
|
|
|
|
| G | Fan | Fan | Activates the system Fan. (Can be Auto, On, or Program controlled) |
|
|
|
|
|
| L | System monitor | System monitor | Activates System Check LED on the front of thermostat. |
|
|
|
|
|
|
|
|
| (Controlled by the system, not the thermostat.) |
|
|
|
|
|
| C | 24VAC common | 24VAC common | Common wire of 24VAC transformer. REQUIRED for thermostat operation. |
|
|
|
|
|
|
|
|
|
|
|
|
|
| AL |
| RS1+ | Remote temperature | Remote temperature | Positive (+) Terminal for Remote Sensor #1. Polarity MUST be maintained. |
|
|
|
|
|
| sensor 1 | sensor 1 |
|
|
| |
|
| N |
| RS1- | Remote sensor 1 (common) | Remote sensor 1 (common) | Negative |
|
|
|
| TIO |
|
|
| ||||
|
|
| RS2+ | Remote temperature | Remote temperature | Positive (+) Terminal for Remote Sensor #2. Polarity MUST be maintained. |
|
| |
|
| P |
|
| sensor 2 | sensor 2 |
|
|
|
|
| O |
|
|
|
|
|
|
|
|
|
| RS2- | Remote sensor 2 (common) | Remote sensor 2 (common) | Negative |
|
| |
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
15
|
|
|
| TABLE B |
|
|
| 15 | |
|
|
| HEAT PUMP |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| EXAMPLES OF DIFFERENT SYSTEM TERMINALS |
|
|
| |||
|
|
|
|
|
|
|
|
|
|
CLIMATE |
|
|
|
|
|
|
|
|
|
TECHNOLOGY |
|
|
| BRYANT, | RHEEM- | TRANE, |
|
|
|
TERMINALS | CARRIER | COLEMAN | COMFORTMAKER | PAYNE | RUUD | WEATHERTRON | YORK | LENNOX (1) | LENNOX (2) |
R | R | R | R | R | R | R | R | R | |
Y1 | Y or Y1 | Y | Y | Y | Y | Y | Y | Y | M |
W2 | W2 | W2 | W1 | W2 | W2 | W | W | W1 | Y |
E | E | E | jumper | E | E | X2 | jumper | E | E |
|
|
| to W2 |
|
|
| to W2 |
|
|
O | O |
| O | O |
| O | O | O | R |
B |
| B |
|
| B |
|
|
|
|
G | G | G | G | G | G | G | G | G | F |
L | L or F | L | L or X | L | L |
| X | L |
|
C | C | X | C, X, X1 | C, C1, X1 | X | B | B | C | X |
|
| Note: W2 wires |
|
|
| Note: |
|
|
|
|
| no connection |
|
|
| T wire no |
|
|
|
|
|
|
|
|
| connection |
|
|
|
NOTE: If your heat pump thermostat does not have an E wire, use the provided jumper wire to connect the E terminal to the W2 terminal, as shown in three examples above. Refer to the Wiring Diagrams on pages