Table 7

CBWMV−36C−090 Blower Performance

0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range ; Factory Settings: Heating Speed − 4, Cooling Speed − 3, Speed Adjust − NORM; Applications with single sided inlets will reduce CFM by approximately 5%.

 

 

 

 

 

 

 

 

 

 

BDC3 Jumper Speed Positions

 

 

 

 

 

 

 

 

 

ADJUST"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1st Stage peed

 

 

 

 

 

Jumper

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

 

3

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cfm

 

L/s

cfm

 

L/s

cfm

 

L/s

cfm

 

L/s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

620

 

290

770

 

365

930

 

440

1010

 

475

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NORM

 

 

 

 

 

 

 

 

 

 

 

 

570

 

270

700

 

330

830

 

390

910

 

430

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

520

 

245

630

 

295

760

 

360

810

 

380

ADJUST"

 

 

 

 

 

HEAT" Speed

 

 

 

 

 

 

 

 

2nd Stage peed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Jumper

 

1

 

2

 

3

 

4

 

1

 

2

 

3

 

4

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cfm

 

L/s

cfm

 

L/s

cfm

 

L/s

cfm

 

L/s

cfm

 

L/s

cfm

 

L/s

cfm

 

L/s

cfm

 

L/s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

820

 

385

1000

 

470

1180

 

555

1340

 

630

890

 

420

1130

 

535

1340

 

630

1450

 

685

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NORM

760

 

360

900

 

425

1070

 

505

1220

 

575

800

 

380

1020

 

480

1220

 

575

1310

 

620

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

675

 

320

810

 

380

950

 

450

1100

 

520

720

 

340

900

 

425

1100

 

520

1180

 

555

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The effect of static pressure and filter resistance is included in air volumes shown. 1st stage COOL is approximately 70% of the same 2nd stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same 2nd stage COOL speed position.

Lennox Harmony zone control applications − Minimum blower speed is 400 cfm. Max cfm is the same as 2nd stage cool position.

Table 8

CBWMV−60C−100 Blower Performance

0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range ; Factory Settings: Heating Speed − 4, Cooling Speed − 3, Speed Adjust − NORM; Applications with single sided inlets will reduce CFM by approximately 5%.

 

 

 

 

 

 

 

 

 

 

BDC3 Jumper Speed Positions

 

 

 

 

 

 

 

 

 

ADJUST"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1st Stage peed

 

 

 

 

 

Jumper

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

 

3

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cfm

 

L/s

cfm

 

L/s

cfm

 

L/s

cfm

 

L/s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

1110

 

525

1250

 

590

1380

 

650

1530

 

720

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NORM

 

 

 

 

 

 

 

 

 

 

 

 

1000

 

470

1130

 

535

1250

 

590

1380

 

650

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

930

 

440

1040

 

490

1130

 

535

1260

 

595

ADJUST"

 

 

 

 

 

HEAT" Speed

 

 

 

 

 

 

 

 

2nd Stage peed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Jumper

 

1

 

2

 

3

 

4

 

1

 

2

 

3

 

4

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cfm

 

L/s

cfm

 

L/s

cfm

 

L/s

cfm

 

L/s

cfm

 

L/s

cfm

 

L/s

cfm

 

L/s

cfm

 

L/s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

1500

 

710

1700

 

800

1880

 

885

2100

 

990

1540

 

725

1760

 

830

1970

 

930

2200

 

1040

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NORM

1370

 

645

1540

 

725

1720

 

810

1920

 

905

1400

 

660

1600

 

755

1800

 

850

1980

 

935

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1250

 

590

1380

 

650

1540

 

725

1720

 

810

1270

 

600

1420

 

670

1600

 

755

1780

 

840

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The effect of static pressure and filter resistance is included in air volumes shown. 1st stage COOL is approximately 70% of the same 2nd stage COOL speed position. Continuous Fan Only speed is approximately 38% of the same 2nd stage COOL speed position.

Lennox Harmony zone control applications − Minimum blower speed is 600 cfm. Max cfm is the same as 2nd stage cool position.

Page 15

CBWMV SERIES

Page 15
Image 15
Lennox International Inc AIR HANDLERS CBWMV−36C−090 Blower Performance, CBWMV−60C−100 Blower Performance

CBWMV, AIR HANDLERS specifications

Lennox International Inc is a renowned leader in the heating, ventilation, and air conditioning (HVAC) industry, known for its commitment to innovation and energy efficiency. Among its impressive lineup of products, the CBWMV air handlers stand out as a reliable solution for optimal indoor climate control.

The CBWMV air handler is designed to provide efficient and effective airflow while being easy to install and maintain. One of the key features of the CBWMV model is its variable speed blower motor, which allows for precise control of airflow and temperature. This innovation not only enhances comfort levels within a space but also contributes to significant energy savings. By adjusting the speed of the motor according to the heating or cooling demand, the system operates more efficiently, reducing energy usage by up to 40% compared to conventional systems.

Another important characteristic of the CBWMV air handlers is their compatibility with a range of heating and cooling systems, including heat pumps and gas furnaces. This versatility makes them an ideal choice for residential and commercial applications alike. The unit’s compact design allows for flexible installation options, accommodating various spaces without compromising performance.

The CBWMV series is also engineered to provide superior air quality. With advanced filtration options, these air handlers can effectively remove dust, allergens, and pollutants from the air, promoting a healthier indoor environment. Many models come equipped with a MERV 16 filter, enhancing the filtration capability, and ensuring that occupants breathe cleaner air.

Durability is another hallmark of the CBWMV line. Constructed with high-quality materials, these air handlers can withstand rigorous use and environmental conditions. The units are designed to require minimal maintenance, with features that facilitate easy access for filter changes and routine servicing.

Additionally, the CBWMV series integrates seamlessly with Lennox’s smart technology solutions, allowing users to monitor and control their HVAC systems remotely. The compatibility with home automation systems ensures that users can optimize comfort settings and efficiency with ease.

In conclusion, Lennox International Inc's CBWMV air handlers offer a remarkable blend of efficiency, comfort, and innovative technology. With features that prioritize energy savings, air quality, versatility, and durability, they represent a forward-thinking choice for modern HVAC needs. Whether for residential or commercial use, these air handlers stand as a testament to Lennox's commitment to excellence in indoor climate management.