Lennox International Inc AIR HANDLERS, CBWMV Filter Assembly & Filters, Plumbing, Electrical

Models: CBWMV AIR HANDLERS

1 20
Download 20 pages 38.01 Kb
Page 8
Image 8
Filter Assembly & Filters

Filter Assembly & Filters

This unit is not equipped with a filter or rack. A field−pro- vided high−velocity filter is required for the unit to operate properly. Table 2 lists recommended filter sizes. A filter must be in place any time the unit is operating.

Table 2

Recommended Filter Sizes

Air Handler

Filter Size

 

 

Cabinet Size

Side Return

Bottom Return

 

 

 

17−1/2"

16 X 25 X 1 (1)

16 X 25 X 1 (1)

21"

16 X 25 X 1 (1)

20 X 25 X 1 (1)

Plumbing

Pipe and Fitting Specifications

Refer to local building and plumbing codes for approved copper pipe and fittings.

Plumbing Procedures

Refer to the installation instructions of the water heating device to be used with the CBWMV unit. Follow the recom- mendations outlined in that instruction as well as govern- ing plumbing codes and practices.

Plumbing Checklist

SFlush water lines between the CBWMV unit and the water heating device before start−up. Normal flushing procedures should be used to rid the system of con- taminants and foreign debris.

SCBWMV units are installed in non-potable systems.

Electrical

Wiring and grounding must conform to the current National Electric Code ANSI/NFPA No. 70, or Canadian Electric Code Part I, CSA Standard C22.1, and local building codes. Refer to following wiring diagrams. See unit name- plate for minimum circuit ampacity and maximum overcur- rent protection size.

Select the proper supply circuit conductors in accor- dance with tables 310−16 and 310−17 in the National Electric Code, ANSI/NFPA No. 70 or tables 1 through 4 in the Canadian Electric Code, Part I, CSA Standard C22.1.

Table 2 CAUTION

USE COPPER CONDUCTORS ONLY.

PlumbingWARNING

Electric shock hazard. Can cause inju- ry or death. Before attempting to per- form any service or maintenance, turn the electrical power to unit OFF at dis- connect switch(es). Unit may have multiple power supplies.

Refer to figure 12 for schematic wiring diagram and trouble- shooting.

Line Voltage (120V)

Line voltage field supply conductors are terminated at the CBWMV unit. The unit is shipped with the line voltage con- nections secured to the lower left coil manifold for left side make−up box installations. For right side make−up box installations, remove the wire tie that holds the line voltage connections and pull excess wires into blower deck/control box area as shown in figure 8.

Install make−up box (provided for line voltage wiring in the unit’s bag assembly) as shown in figure 9.

Make−up Box Wiring

WIRES SHOWN AS SHIPPED,

ROUTED FOR LEFT SIDE

MAKE−UP BOX INSTALLATION Pipe and Fitting Specifications

FOR RIGHT SIDE MAKE−UP

BOX INSTALLATION

REMOVE WIRE TIE,

PULL EXCESS WIRE INTO

BLOWER DECK / CONTROL

BOX AREA.

Figure 8

Interior Make−Up Box Installation

 

MAKE−UP

 

BOX

MAKE−UP

 

BOX

 

LEFT SIDE

RIGHT SIDE

 

Figure 9

Page 8

505047 09/06

Page 8
Image 8
Lennox International Inc AIR HANDLERS Filter Assembly & Filters, Plumbing, Electrical, Table Recommended Filter Sizes