CLEARANCE ON ALL SIDES
MINIMUM CLEARANCE
ABOVE UNIT
6 (152)
12 (305)
36 (914)
ACCESS PANEL
NOTES:
SClearance to one of the other three
30 (762) |
| sides must be 36 inches (914mm). |
| ||
|
|
|
SClearance to one of the remaining
two sides may be 12 inches (305mm) and the final side may be 6 inches (152mm).
LINE SET
CONNECTIONS
48 (1219)
MINIMUM CLEARANCE BETWEEN |
|
TWO UNITS |
|
| ACCESS PANEL |
24 (610) | LINE SET |
| |
| CONNECTIONS |
Figure 4. Installation Clearances
DETAIL A
INSTALL UNIT AWAY
FROM WINDOWS
DETAIL B
Install unit level or, if on a slope, maintain slope tolerance of 2 degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away from building structure.
DISCHARGE AIR
BUILDING
STRUCTURE
TWO 90_ ELBOWS INSTALLED IN LINE SET
WILL REDUCE LINE SET VIBRATION
MOUNTING
SLAB
GROUND LEVEL
Figure 5. Placement, and Slab Mounting
New Unit Placement
See Unit Dimensions on page 2 for sizing mounting slab, platforms or supports. Refer to figure 4 for mandatory installation clearance requirements.
POSITIONING CONSIDERATIONS
CAUTION
In order to avoid injury, take proper precaution when lifting heavy objects.
Consider the following when positioning the unit:
SSome localities are adopting sound ordinances based on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.
SWhen possible, do not install the unit directly outside a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 5, detail A.
Page 7
14ACX SERIES