Lennox International Inc Merit Series 14ACX Units Detail A, Detail B, New Unit Placement

Models: Merit Series 14ACX Units CONDENSING UNITS

1 30
Download 30 pages 43.35 Kb
Page 7
Image 7
DETAIL A

CLEARANCE ON ALL SIDES

MINIMUM CLEARANCE

ABOVE UNIT

6 (152)

12 (305)

36 (914)

ACCESS PANEL

NOTES:

SClearance to one of the other three

30 (762)

 

sides must be 36 inches (914mm).

 

 

 

 

SClearance to one of the remaining

two sides may be 12 inches (305mm) and the final side may be 6 inches (152mm).

LINE SET

CONNECTIONS

48 (1219)

MINIMUM CLEARANCE BETWEEN

 

TWO UNITS

 

 

ACCESS PANEL

24 (610)

LINE SET

 

 

CONNECTIONS

Figure 4. Installation Clearances

DETAIL A

INSTALL UNIT AWAY

FROM WINDOWS

DETAIL B

Install unit level or, if on a slope, maintain slope tolerance of 2 degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away from building structure.

DISCHARGE AIR

BUILDING

STRUCTURE

TWO 90_ ELBOWS INSTALLED IN LINE SET

WILL REDUCE LINE SET VIBRATION

MOUNTING

SLAB

GROUND LEVEL

Figure 5. Placement, and Slab Mounting

New Unit Placement

See Unit Dimensions on page 2 for sizing mounting slab, platforms or supports. Refer to figure 4 for mandatory installation clearance requirements.

POSITIONING CONSIDERATIONS

DETAIL B CAUTION

In order to avoid injury, take proper precaution when lifting heavy objects.

Consider the following when positioning the unit:

SSome localities are adopting sound ordinances based on the unit’s sound level registered from the adjacent property, not from the installation property. Install the unit as far as possible from the property line.

SWhen possible, do not install the unit directly outside a window. Glass has a very high level of sound transmission. For proper placement of unit in relation to a window see the provided illustration in figure 5, detail A.

Page 7

14ACX SERIES

Page 7
Image 7
Lennox International Inc Merit Series 14ACX Units, CONDENSING UNITS Detail A, Detail B, New Unit Placement