Lennox International Inc 16L24, LB-89657A, 16L23 II- Internal Filter Rack Used with kit CAT#16L25

Models: 16L24 16L25 LB-89657B LB-89658A LB-89657A 16L23

1 8
Download 8 pages 2.55 Kb
Page 4
Image 4
II- Internal Filter Rack (Used with kit CAT#16L25)

Note - It is recommended that rack be converted to 20 inch filter size if filter is installed elsewhere in return air duct.

3-In applications where rack uses a 16 inch (50.8cm) filter, remove filler piece before cutting rack opening. See figure 4.

4 - Cut four strips from rollofadhesive-backedfoam tape (provided) to fit filter rack flanges, Apply to flanges.

5 - Secure filter rack to cabinet as shown in figure 4. 6 - Cut opening in filter rack as shown in figure 4,

7 - In applications where rack uses a 16 inch (50,8cm) filter, remove rack from cabinet, re-install filler piece, then re-install rack to cabinet.

8-Install existing filter, unless filter is located elsewhere in the return air duct,

9- Attach door to filter rack with thumb screws provided.

II- Internal Filter Rack (Used with kit CAT#16L25)

Note - If filter is not to be located inside of unit, installation of this filter kit is not required.

1 - Lay G26 unit on its side and cut out return air

opening in cabinet at knockout guides, See G26 installation instructions.

2 - Install filter rack top and bottom inside unit as shown in figure 5, tn right side installations wiring must be carefully worked around.

3 - Install existing filter,

4 - Slide door into filter rack bottom seam and align with filter rack top securing hole. Attach with thumb screws provided.

5- Securewiring awayfrom filter access areawith two provided wire ties. Use existing screws in existing screw locations to prevent accidental damage to control board(s)/wiring by drilling of new holes.

B - Supply Air Transition Installation

1 - Cut four strips from roll ofadhesive-backedfoam tape (provided) to fit supply air transition flanges at G26 unit connection. Apply to flanges. See figure 4 or 5,

2- Position supply air transition on unit top as shown in figure 4 or 5.

3- If required, internally insulate transition with foil-faced insulation (field provided) and fasten with kit provided insulation pins and washers,

4- Use four screws and/or bend cabinet flanges over transition tips to secure transition.

C - Unit Installation

1 - Align unit with existing supply air plenum (coil

cabinet in air conditioning applications) and return air plenum.

Note - If required, use existing G14 isomode pads to achieve this alignment.

2 - Make connections to unit, In bottom return air applications, follow the instructions provided with the G26 unit, note especiallythe warnings in the "Return Air Opening Guidelines" section.

3 - ff air conditioning coil was removed, re-install coil, reconnect line set and coil drain. See

condensing unit installation instructions for re-processing of refrigerant system.

Note - Coil drain line must not be connected to heat exchanger condensate drain line. If lines were connected, debris from evaporator could affect heat exchanger operation.

4- Make tow voltage wiring entrance to unit on opposite side from return air connection to

prevent blocking filter access. Connect as illustrated in G26 installation instructions.

5 - Connect high voltage wiring as outlined in G26 installation instructions,

6- Connect gas piping as outlined in G26 installation instructions.

Consult local codes for flexible connector

installation restrictions on G26 furnace.

7 - Connect venting as outlined in G26 installation instructions.

Note - Mufflers can not be used in G26 installation. Check existing venting for size (diameter and length). It should meet the specifications as outlined in G26 installation instructions.

8 - Connect heat exchanger condensate drain line as shown in figure 6 and as outlined in G26 unit installation instructions, (A 1/2" PVCto 1/2" CPVC bushing is provided for connecting PVC to existing CPVC condensate line,)

9 - Continue with Unit Start-up Section as outlined in G26 installation instructions.

Note - See G26 installation instructions for heat anticipation settings.

Page 4

Page 4
Image 4
Lennox International Inc 16L24 II- Internal Filter Rack Used with kit CAT#16L25, B - Supply Air Transition Installation