Lennox International Inc TUA75S, TUA125S Horizontal Venting - Residential Installation, Page

Models: TUA45S T-CLASS TM SEPARATED COMBUSTION UNIT HEATERS TUA75S TUA100S TUA60S TUA125S

1 21
Download 21 pages 56.1 Kb
Page 10
Image 10
TABLE 3

TABLE 3

VERTICAL VENT REQUIREMENTS

MODEL

INSTALLATION

FLUE TYPE

FLUE

AIR

VENT CAP

OTHER

 

 

AIR INLET TYPE

DIA.

INLET

 

 

 

 

 

 

DIA.

 

 

45

COMMERCIAL

SINGLE WALL

3”

3”

U.L. APPROVED

MAY USE ONE

 

or

SINGLE WALL or

 

 

 

SECTION OF B-

 

RESIDENTIAL

METAL FLEX VENT

 

 

 

VENT

45

COMMERCIAL

TYPE B VENT

3”

3”

U.L. APPROVED

 

 

or

SINGLE WALL or

 

 

 

 

 

RESIDENTIAL

METAL FLEX VENT

 

 

 

 

45

COMMERCIAL

CONCENTRIC

3”

3”

4” CONCENTRIC

 

 

or

SINGLE WALL or

 

 

VENT/ ADAPTER/CAP

 

 

RESIDENTIAL

METAL FLEX VENT

 

 

KIT REQUIRED

 

60, 75

COMMERCIAL

SINGLE WALL

4”

4”

U.L. APPROVED

MAY USE ONE

 

or

SINGLE WALL or

 

 

 

SECTION OF B-

 

RESIDENTIAL

METAL FLEX VENT

 

 

 

VENT

60, 75

COMMERCIAL

TYPE B VENT

4”

4”

U.L. APPROVED

 

 

or

SINGLE WALL or

 

 

 

 

 

RESIDENTIAL

METAL FLEX VENT

 

 

 

 

60, 75

COMMERCIAL

CONCENTRIC

4”

4”

4” CONCENTRIC

 

 

or

SINGLE WALL or

 

 

VENT/ ADAPTER/CAP

 

 

RESIDENTIAL

METAL FLEX VENT

 

 

KIT REQUIRED

 

100, 125

COMMERCIAL

SINGLE WALL

5”

4”

U.L. APPROVED

MAY USE ONE

 

or

SINGLE WALL or

 

 

 

SECTION OF B-

 

RESIDENTIAL

METAL FLEX VENT

 

 

 

VENT

100, 125

COMMERCIAL

TYPE B VENT

5”

4”

U.L. APPROVED

 

 

or

SINGLE WALL or

 

 

 

 

 

RESIDENTIAL

METAL FLEX VENT

 

 

 

 

100, 125

COMMERCIAL

CONCENTRIC

5”

4”

5” CONCENTRIC

 

 

or

SINGLE WALL or

 

 

VENT/ ADAPTER/CAP

 

 

RESIDENTIAL

METAL FLEX VENT

 

 

KIT REQUIRED

 

HORIZONTAL VENTING - RESIDENTIAL INSTALLATION

UPWARD SLOPE

MAY BE SINGLE WALL (26 GSG) GALV. OR EQUIVALENT STAINLESS STEEL SEALED ACCORDING TO THESE INSTALLATION INSTRUCTIONS OR A SINGLE SECTION OF TYPE B-1 VENT. SLOPE:+ 1/4 INCH FOR 1 FOOT RUN MINIMUM.

VENT TERMINATION

(TERMINATIONS MAY USE WIRE MESH BIRD SCREEN)

12” (30.5 CM) MIN. FROM

AIR INLET TO VENT TERMINATION (MAY

BE HORIZONTAL OR VERTICAL CLEARANCE)

12” (30.5 CM) MINIMUM ABOVE HIGHEST SNOWFALL

HORIZONTAL VENTING - RESIDENTIAL INSTALLATION 12” (30.5 CM) MIN. FROM WALL TO

VENT TERMINATION

LISTED THIMBLE

THROUGH

COMBUSTIBLE WALL

AIR INLET TERMINATION

NOTE - MINIMUM HORIZONTAL LENGTH 3 FT. (91.4 CM) NOT INCLUDING TERMINATION. MAXIMUM HORIZONTAL VENT LENGTH 5 FT. (1.5M) PLUS ONE 90-DEGREE ELBOW.

GROUND LEVEL

COMMON VENTING NOT ALLOWED WHEN HORIZONTALLY VENTING THE UNIT HEATER.

FIGURE 6

Page 9

Page 10
Image 10
Lennox International Inc TUA75S Horizontal Venting - Residential Installation, Table Vertical Vent Requirements, Page