VENT AND AIR INTAKE TERMINATION ON SINGLE WALL VENT
SINGLE WALL TERMINATION
ROOF FLASHING
DOUBLE WALL (TYPE
ROOF FLASHING |
ROOF PITCHED |
FROM 0" TO 45" |
SHALL NOT BE A CONCEALED SPACE
2" CLEARANCE |
THIMBLE |
ROOF PITCHED |
|
FROM 0" TO 45" |
|
12" MAX | CLEARANCE TO BE |
| |
| AS SPECIFIED ON |
| TYPE “B" VENT PIPE. |
SEAL JOINT BETWEEN SINGLE WALL VENT AND “B" VENT AND THE ANNULAR SPACE OF THE “B" VENT.
FIGURE 2
C-Horizontal Venting - General
Common venting is not allowed with horizontal vent.
The minimum horizontal vent length is three feet (914mm). 1- If possible, do not terminate the horizontal vent through a wall that is exposed to prevailing wind. Exposure to excessive winds can affect unit performance. If such a termination is necessary, use a wind block to protect the vent termination from direct
winds.
2- Vent termination must be free from obstructions and at least 12" (306mm) above grade level and maximum snow height.
3- Do not terminate vent directly below roof eaves or above a walkway, or any other area where condensate dripping may be troublesome and may cause some staining. Avoid windows where steam may cause fogging or ice buildup.
4- When horizontally vented, minimum clearance for termination from any door, window, gravity air inlet, gas or electric meter, regulators, and relief equipment is 4 ft. (1.2m) for U.S. installations. Refer to NFPA 54/ANSI Z223.1 in the U.S.A. and CSA B149.1 and .2 in Canada or with authorities having local jurisdiction. In Canada, vent termination must have a minimum 6 ft. (1.8mm) horizontal clearance from gas and electric meters and relief devices as specified in the Canadian B149.1, Natural Gas Installation Code.
5- Vent termination must be a minimum of 4' (1.2m) below or 4’ (1.2m) horizontally from any soffit vent or
6- Vent must be a minimum of 6' from an inside corner formed by two exterior walls. If possible, leave a 10' clearance.
7- Vent termination must be a minimum of 10' (3m) from any forced air inlet (includes fresh air inlet for other appliances, such as a dryer).
8- When termination is routed through an exterior combustible wall the vent must be supported using a listed clearance thimble. Where local authorities permit, a single section of type
used as an alternative to the thimble. When using a type
9- All horizontal vents must terminate with a tee or with a cap as specified in table 4. Opening end of tee used for termination must face downward. Addition of ¼” (6mm) mesh corrosion resistant material as a bird screen in the tee or cap openings may be used.
9- For horizontal venting, the vent pipe shall be supported with hangers no more than 3ft. (1m) apart to prevent movement after installation.
D-Horizontal Venting-Commercial
1- Horizontal commercial installations are for buildings that are not attached to living spaces. The vent may be single wall vent material installed according to
the sections Venting
2- Refer to table 2 for maximum vent lengths. The vent pipe diameter for horizontal commercial installations shall be 3” (76mm) on 45 units, 4” (100mm) on 60/75 units, 5” (127mm)on 100/125 units.
Page 6