F-Horizontal Venting-Residential Two Pipes

F-Horizontal Venting-Residential Two Pipes

1-For horizontal residential installations these units are certified as Category I appliances. The vent may be single wall material minimum 25 GSG (0.46mm) galvanized steel or equivalent grade stainless steel or a single section of type B-1 vent installed according to the sections Venting A-General Recommendations and Requirements and C-Horizontal Venting General and F-HorizontalVenting–Residential Two Pipes. Refer to figure 6.

2-The vent pipe diameter for horizontal residential installations shall be 4” (100mm) on 45 units and 5” (127mm) on 60/75/100/125 units. Refer to table 4 for vent diameter and termination requirements.

3-The maximum vent length is 5’ (1.5m) plus one 90- degree elbow.

4-The vent must maintain a ¼” rise per foot of slope upwards toward the termination

TABLE 4

HORIZONTAL VENT REQUIREMENTS

MODEL

INSTALLATION

FLUE TYPE

FLUE DIA.

VENT CAP

MAX. VENT

 

 

AIR INLET TYPE

INLET AIR

INLET AIR CAP

LENGTH (MIN.

 

 

 

DIA.

 

VENT LENGTH 3’)

45

RESIDENTIAL

SINGLE WALL

4”

TEE or

5’ MAY USE ONE

 

 

 

 

4” BELMONT

SECTION OF

 

 

SINGLE WALL PIPE or

3”

TEE or

B-VENT

 

 

METAL FLEX VENT

 

3” BELMONT

 

45

RESIDENTIAL

CONCENTRIC

4”

4” CONCENTRIC

5’

 

 

SINGLE WALL PIPE or

3”

VENT/ ADAPTER/CAP

 

 

 

METAL FLEX VENT

 

KIT REQUIRED

 

45

COMMERCIAL

SINGLE WALL

3”

TEE or

25’ MAY USE ONE

 

 

 

 

3” BELMONT

SECTION OF

 

 

SINGLE WALL PIPE or

3”

TEE or

B-VENT

 

 

METAL FLEX VENT

 

3” BELMONT

 

45

COMMERCIAL

CONCENTRIC

3”

4” CONCENTRIC

25’

 

 

SINGLE WALL PIPE or

3”

VENT/ ADAPTER/CAP

 

 

 

METAL FLEX VENT

 

KIT REQUIRED

 

60, 75

RESIDENTIAL

SINGLE WALL

5”

TEE or

5’ MAY USE ONE

 

 

 

 

5” BELMONT

SECTION OF

 

 

SINGLE WALL PIPE or

4”

TEE or

B-VENT

 

 

METAL FLEX VENT

 

4” BELMONT

 

60, 75

RESIDENTIAL

CONCENTRIC

4”

4” CONCENTRIC

5’

 

 

SINGLE WALL PIPE or

4”

VENT/ ADAPTER/CAP

 

 

 

METAL FLEX VENT

 

KIT REQUIRED

 

60, 75

COMMERCIAL

SINGLE WALL

4”

TEE or

25’ MAY USE ONE

 

 

 

 

4” BELMONT

SECTION OF B-

 

 

SINGLE WALL PIPE or

4”

TEE or

VENT

 

 

METAL FLEX VENT

 

4” BELMONT

 

60, 75

COMMERCIAL

CONCENTRIC

4”

4” CONCENTRIC

25’

 

 

SINGLE WALL PIPE or

4”

VENT/ ADAPTER/CAP

 

 

 

METAL FLEX VENT

 

KIT REQUIRED

 

100, 125

RESIDENTIAL

SINGLE WALL

5”

TEE or

5’ MAY USE ONE

 

 

 

 

5” BELMONT

SECTION OF

 

 

SINGLE WALL PIPE or

4”

TEE or

B-VENT

 

 

METAL FLEX VENT

 

4” BELMONT

 

100, 125

COMMERCIAL

SINGLE WALL

5”

TEE or

5’ MAY USE ONE

 

 

 

 

5” BELMONT

SECTION OF

 

 

SINGLE WALL PIPE or

4”

TEE or

B-VENT

 

 

METAL FLEX VENT

 

4” BELMONT

 