ADJUSTMENTS
Limit Control
The limit control switch is factory set and not field adjustable.
Louver Vane Adjustment
Rotate louver vanes to direct airflow upward, downward, straight, or any combination of these directions.
Combustion Air Inducer Proving Switch
This combustion air inducer proving switch checks for proper combustion air inducer operation before allowing an ignition trial. The switch is factory set and no field adjustment is necessary.
Flame Rollout Switch
The flame rollout switch(es) on 45, 60 or 75 units are located on the burner box top, behind the ignition control board. The flame rollout switch on 100 or 125 units is located on the manifold bracket above the top burner. This normally closed switch opens on a temperature rise. Check for adequate combustion air and proper venting before manually resetting switch.
TABLE 6
NATURAL GAS MANIFOLD PRESSURES - in.wg. (kPa)
ALTITUDE FT. (M)
MODEL | ||||||||||
| ||||||||||
TUA045SN | 3.5 (0.87)* | 2.7 (0.67) | 2.5 (0.62) | 2.2 (0.55) | 2.0 (0.50) | 1.8 (0.45) | 1.6 (0.40) | 1.4 (0.35) | 1.3 (0.32) | |
TUA060SN | 3.5 (0.87)* | 2.7 (0.67) | 2.5 (0.62) | 2.2 (0.55) | 2.0 (0.50) | 1.8 (0.45) | 1.6 (0.40) | 1.4 (0.35) | 1.3 (0.32) | |
TUA075SN | 3.5 (0.87)* | 2.7 (0.67) | 2.5 (0.62) | 2.2 (0.55) | 2.0 (0.50) | 1.8 (0.45) | 1.6 (0.40) | 1.4 (0.35) | 1.3 (0.32) | |
TUA100SN | 3.5 (0.87)* | 2.7 (0.67) | 2.5 (0.62) | 2.2 (0.55) | 2.0 (0.50) | 1.8 (0.45) | 1.6 (0.40) | 1.4 (0.35) | 1.3 (0.32) | |
TUA125SN | 3.5 (0.87)* | 2.7 (0.67) | 2.5 (0.62) | 2.2 (0.55) | 2.0 (0.50) | 1.8 (0.45) | 1.6 (0.40) | 1.4 (0.35) | 1.3 (0.32) |
*No adjustment required.
Page 17