Lennox International Inc TUA45S, TUA125S Gas Flow, LP/PROPANE GAS MANIFOLD PRESSURES - in.wg. kPa

Models: TUA45S T-CLASS TM SEPARATED COMBUSTION UNIT HEATERS TUA75S TUA100S TUA60S TUA125S

1 21
Download 21 pages 56.1 Kb
Page 19
Image 19
LP/PROPANE GAS MANIFOLD PRESSURES - in.wg. (kPa )

TABLE 7

LP/PROPANE GAS MANIFOLD PRESSURES - in.wg. (kPa )

ALTITUDE FT. (M)

MODEL

0-2000

2001-3000

3001-4000

4001-5000

5001-6000

6001-7000

7001-8000

8001-9000

9001-10000

(0-610)

(610-914)

(915-1219)

(1220-1524)

(1524-1829)

(1829-2134)

(2134-2438)

(2439-2743)

(2744-3048)

 

 

 

 

 

 

 

 

 

 

 

TUA045SL

9.5 (2.37)*

7.4 (1.84)

6.7 (1.67)

6.1 (1.52)

5.5 (1.37)

4.9 (1.22)

4.4 (1.10)

3.9 (0.97)

3.4 (0.85)

TUA060SL

9.5 (2.37)*

7.4 (1.84)

6.7 (1.67)

6.1 (1.52)

5.5 (1.37)

4.9 (1.22)

4.4 (1.10)

3.9 (0.97)

3.4 (0.85)

TUA075SL

9.5 (2.37)*

7.4 (1.84)

6.7 (1.67)

6.1 (1.52)

5.5 (1.37)

4.9 (1.22)

4.4 (1.10)

3.9 (0.97)

3.4 (0.85)

TUA100SL

9.0 (2.24)*

7.0 (1.74)

6.4 (1.59)

5.8 (1.44)

5.2 (1.30)

4.7 (1.17)

4.2 (1.05)

3.7 (0.92)

3.2 (0.80)

TUA125SL

9.0 (2.24)*

7.0 (1.74)

6.4 (1.59)

5.8 (1.44)

5.2 (1.30)

4.7 (1.17)

4.2 (1.05)

3.7 (0.92)

3.2 (0.80)

*No adjustment required.

Gas Flow

Check for proper gas flow to the unit heater.

1.Operate unit at least 15 minutes before checking gas flow. Determine the time in seconds for one revolution of gas through the meter.

2.Compare the number of seconds and the gas meter size in table 8 to determine the gas flow rate. Multiply the gas flow rate by the heating value to determine the unit input rate. If manifold pressure is correct and the unit input rate is incorrect, check gas orifices for proper size and restriction.

3.Remove temporary gas meter if installed.

NOTE – To obtain accurate reading, shut off all other gas appliances connected to meter.

TABLE 8

Gas Flow Rate (Ft.3/Hr.)

Seconds for 1

 

 

Gas Meter Size

Revolution

½ cu ft Dial

1 cu ft Dial

10

 

180

360

12

 

150

300

14

 

129

257

16

 

113

225

18

 

100

200

20

 

90

180

22

 

82

164

24

 

75

150

26

 

69

138

28

 

64

129

30

 

60

120

32

 

56

113

34

 

53

106

36

 

50

100

38

 

47

95

40

 

45

90

42

 

43

86

44

 

41

82

46

 

39

78

48

 

38

75

50

 

36

72

52

 

35

69

54

 

33

67

56

 

32

64

58

 

31

62

60

 

30

60

Natural = 1000 btu/cu ft

 

LP = 2500 btu/cu ft

Note: Table assumes standard temperature (60°F), barometric pressure (30 in Hg), and fuel heating values (btu/cu ft). Fuel heating values may vary, contact local fuel supplier to obtain actual heating value of fuel being supplied.