Installing Indoor Metering Device
This outdoor unit is designed for use in systems that use |
| coil. In applications where an uncased coil is being | ||||||
expansion valve metering devices at the indoor coil. |
| installed in a field−provided plenum, install the expansion | ||||||
See the Lennox XC16 Engineering Handbook for |
| valve in a manner that will provide access for field servicing | ||||||
approved expansion valve kit match−ups. The expansion |
| of the expansion valve. Refer to below illustration for | ||||||
valve unit can be installed internal or external to the indoor |
| reference during installation of expansion valve unit. | ||||||
INDOOR EXPANSION VALVE INSTALLATION | A | Remove the field−provided fitting that temporary | 1/2 Turn | |||||
TWO PIECE |
|
|
| reconnected the liquid line to the indoor unit’s distributor |
|
|
|
|
(Uncased Coil Shown) |
| assembly. |
|
| 12 |
| ||
PATCH PLATE |
| 1011 | 1 2 | |||||
(UNCASED | B | Install one of the provided Teflon® rings around the |
| |||||
COIL ONLY) | LIQUID LINE | STUB |
| stubbed end of the expansion valve and lightly lubricate | 9 |
|
| 3 |
END EXPANSION |
|
|
| |||||
| ORIFICE |
|
|
| ||||
| VALVE |
| the connector threads and expose surface of the Teflon® | 8 |
|
| 4 | |
| HOUSING |
|
|
| ||||
DISTRIBUTOR |
|
| ring with refrigerant oil. |
| 7 6 | 5 | ||
|
|
|
| |||||
TUBES |
|
|
|
|
|
|
| |
| TEFLON® | C Attach the stubbed end of the expansion valve to the |
|
|
|
| ||
|
|
|
|
|
| |||
|
| RING |
| liquid line orifice housing. Finger tighten and use an |
|
|
|
|
|
|
|
| appropriately sized wrench to turn an additional 1/2 turn |
|
|
|
|
|
|
|
| clockwise as illustrated in the figure above, or 20 ft−lb. |
|
|
|
|
TEFLON® RING
SENSING
LINE
DPlace the remaining Teflon® washer around the other end of the expansion valve. Lightly lubricate connector threads and expose surface of the Teflon® ring with refrigerant oil.
DISTRIBUTOREQUALIZER
ASSEMBLY LINE
LIQUID LINE
ASSEMBLY WITH
BRASS NUT
EAttach the liquid line assembly to the expansion valve. Finger tighten and use an appropriately sized wrench to turn an additional 1/2 turn clockwise as illustrated in the figure above or 20 ft−lb.
SENSING BULB INSTALLATION
MALE EQUALIZER LINE | VAPOR | |
FITTING (SEE | ||
LINE | ||
EQUALIZER LINE | ||
| ||
INSTALLATION FOR |
| |
FURTHER DETAILS) |
|
Sensing bulb insulation is required if mounted external to the coil casing. sensing bulb installation for bulb positioning.
AAttach the vapor line sensing bulb in the proper orientation as illustrated to the right using the clamp and screws provided.
NOTE
and expansion bulb before insulating the sensing bulb once LIQUID LINE installed.
BConnect the equalizer line from the expansion valve to the equalizer vapor port on the vapor line. Finger tighten the flare nut plus 1/8 turn (7 ft−lbs) as illustrated below.
| 1/8 Turn | ||
| 11 12 | 1 | |
10 |
| 2 | |
9 |
|
| 43 |
8 | 7 | 6 | 5 |
EQUALIZER LINE INSTALLATION
ARemove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.
BRemove and discard either the flare seal cap or flare nut with copper flare seal bonnet from the equalizer line port on the vapor line as illustrated in the figure to the right.
VAPOR LINE | ON LINES SMALLER THAN |
7/8", MOUNT SENSING | |
| BULB AT EITHER THE 3 OR |
| 9 O’CLOCK POSITION. |
| 12 |
BULB | BULB |
FLARE SEAL CAP
OR
FLARE NUT | VAPOR LINE |
|
|
| |
|
| ON 7/8" AND LARGER LINES, |
|
| MOUNT SENSING BULB AT |
COPPER FLARE |
| EITHER THE 4 OR 8 O’CLOCK |
SEAL BONNET | 12 | POSITION. NEVER MOUNT ON |
| BOTTOM OF LINE. | |
MALE BRASS EQUALIZER | BULB | BULB |
LINE FITTING |
| |
|
|
VAPOR LINE | NOTE OM OF LINE. |
Figure 10. Installing Indoor Expansion Valve
Page 16
506637−01 11/10