INSTALLATION

CHIMNEY HEIGHT REQUIREMENTS

The chimney must extend 3 feet (914 mm) above the level of roof penetration and a minimum of 2 feet (610 mm) higher than any roof surface within 10 feet (305 cm) (see below). Check with your local building officials for any ad- ditional requirements for your area.

Due to prevailing winds, local terrain, adjacent tall trees, a hill, or ravine near the home, or adjacent structures, addi- tional chimney height or a special chimney cap may be required to ensure optimum performance.

The 2’ by 10’ Rule for Vent Termination

Requires A Listed

3’ (915mm)

Termination Cap

2’ (610mm)

10’ (305 cm)

The top of the flue must be 2’ (610 mm) higher than any part of the roof within 10’ (305 cm) horizontal and a minimum of 3’ (915 mm) higher than the highest point of roof penetration.

For Manufactured (Mobile) Homes Only: Portions of the chimney and termination that exceed an elevation of 13½ feet above ground level may be designed to be removed for transporting the manufactured (mobile) home.

PAGE 9

Page 9
Image 9
LG Electronics 1400HT operation manual Chimney Height Requirements, 2’ by 10’ Rule for Vent Termination