FunctionofOutdoor Unit

Operation

Outdoor Unit Two Comp algorithmFunction Operating Stepof LEV ControlOutdoor Unit Out door Fan Control R/Valve Control(Heating Model Only) Defrost Function Oil Return System Comp Overload Protection High Pressure ProtctionManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

Outdoor Unit

Manual background Two Comp algorithm

Inverter Comp is first priority and then Constant Comp is turning on responding to load condtion.

Manual background Operating Step

Compressor step varies considering condition such as room temp,outdoor temp, operating room number,Temp gap between room temp and set temp and so on.

Manual background LEV Control

LEV pulse is modulated to keep constant superheat or subcooling.

Manual background Out door Fan Control

Outdoor fan operates at High or Off to respond to the load condition.

Manual background R/Valve Control(Heating Model Only)

Convert R/Valve to change cooling to heating, heating to cooling.

Manual background Defrost Function

After 45 min heating operation, check the defrost condition and if outdoor pipe temp is below -

5°C(23°F) and released from deice operation in case outdoor pipe temp is over 12°C(53.6°F) or 9 min cooing mode.

To deice outdoor heat exchanger in low temp condtion, convert operating mode from heating to

Manual background Oil Return System

In single(one) comp operation duration, another comp will operate for 30 seconds every 1 hours.

Manual background Comp Overload Protection

To protect comp from being overload, protector will turn off the comp.

Manual background High Pressure Protction

If cycle pressure is too high(around 36.7 kgf/cm2), it will turn off comp A

Service Manual 47