Troubleshooting Guide

Additional gas charging

(Gas leakage)

When refrigerant is insufficient by leakage, recharge the unit with the refrigerant up to normal oper- ating suction pressure.

Use the graph or the equation below to get operating suction pressure according to indoor and out- door temperature.

Suction pressure was measured at 3-way valve service port after operating the unit for 10 minutes.

The method of using graph

-Find outdoor temperature.

-Find indoor temperature onto the curve of outdoor temperature.

-Read suction pressure at the axis of ordinates.

The method of using equation

-. Calculate suction pressure after putting indoor and outdoor temperature into the equation.

Operating Suction Pressure (For R410A)

(According to Indoor & Outdoor Temperature)

Suction Pressure (Kg/cm2.g)

 

(At operating the Unit for 10 minutes)

13

 

12

50˚C

 

11

40˚C

10

30˚C

9

20˚C

8

10˚C

0˚C

 

7

6

5

5

10

15

20

25

30

35

40

Indoor Temp. (˚C)

Outdoor Temp. (˚C)

P = 3 + 0.0123 x Tout1.5 + 0.8 x Tin0.5

Where, P : Suction Pressure(kg/cm2.g)

Tout : Outdoor Temperature(˚C)

Tin : Indoor Temperature(˚C)

Copyright ©2007 LG Electronics. Inc. All right reserved.

- 50 -

Only for training and service purposes

LGE Internal Use Only

 