27

APPLICATION DATA — 569D072-120, 576C090-120, 569F120

OPERATING LIMITS

NOTES:
1. Select air handler at no less than 300 cfm/ton (nominal condens-
ing unit capacity).
2. Total combined draw of the field-supplied liquid line solenoid valve
and air handler fan contactor must not exceed 22 va. If the speci-
fied va must be exceeded, use a remote relay to control the load.

1. LIQUID LINE — For applications with liquid lift greater than

20 ft, use 1/2-in. liquid line where 3/8in.isshown;use5/8-in.

liquid line where 1/2in. is shown. The maximum liquid lift is

60 ft.

MAXIMUM REFRIGERANT CHARGE

2. REFRIGERANT PIPING — It is recommended that the

refrigerant piping for all commercial split systems include a

liquid line solenoid valve, a liquid line filter drier, and a sight

glass.

For refrigerant lines longer than 75 lineal ft, a liquid line

solenoid valve and a suction accumulator are required.

Refer to the Refrigerant Specialties table.

MINIMUM OUTDOOR-AIR OPERATING

TEMPERATURE

*Unit has one step of unloading.

REFRIGERANT PIPING SIZES

LEGEND
L—Liquid Line S—Suction Line
NOTES:
1. Pipe sizes are based on a 2°F loss for liquid and suction lines.
2. Pipe sizes are based on the maximum linear length, shown for
each column, plus a 50% allowance for fittings.
3. Charge units with R-22 in accordance with unit installation
instructions.

REFRIGERANT SPECIALTIES PART NUMBERS

*Bushings required.
Maximum Cooling Outdoor 115 F
Minimum Outdoor Ambient
See Minimum Outdoor-Air
Operating Temperature
table at right.
Minimum Return-Air
Temperature 55 F
Maximum Return-Air
Temperature 95 F
Normal Acceptable Saturation
Suction Temperature Range 25 to 55 F
Maximum Discharge
Temperature 275 F
Minimum Discharge Superheat 60 F
UNIT
SIZER-22 (lb)
569D
072 17.3
090 34.2
120 34.2
576C 120 34.2
569F 120 (2) 17.1
UNIT
SIZE
COMPR
CAPACITY
COND
TEMP
(F)
MINIMUM
OUTDOOR TEMP
(F)
Std
With
Motormaster®
Control
569D
072 100% 90 35
–20
090 100% 90 35
120 100% 90 35
576C 120* 100% 90 35
67% 80 35
569F 120 100% 90 35
UNIT
SIZE
LINEAR LENGTH OF PIPING — FT
0-25 25-50 50-75 75-100
Line Size (in. OD)
LSLSLSLS
569D
072 3/811/83/811/83/811/83/811/8
090 3/811/81/211/81/211/81/211/8
120 1/213/81/213/81/213/81/213/8
576C 120 1/213/81/213/81/213/81/213/8
569F 120 (2) 3/8(2) 11/8(2) 3/8(2) 11/8(2) 3/8(2) 11/8(2) 3/8(2) 11/8
UNIT LIQUID LINE
SIZE (in.)
LIQUID LINE
SOLENOID VALVE (LLSV)
LLSV
COIL
SIGHT
GLASS
FILTER
DRIER
SUCTION LINE
ACCUMULATOR
569D072 3/8200RB5T3M AMG/24V AMI-1TT3 P502-8304S* S-7063S*
569D090
3/8200RB5T3M AMG/24V AMI-1TT3 P502-8304S* S-7063S*
1/2200RB5T4M AMG/24V AMI-1TT4 P502-8304S S-7063S*
569D120 1/2200RB6T4M AMG/24V AMI-1TT4 P502-8307S* S-7063
576C120
1/2200RB6T4M AMG/24V AMI-1TT4 P502-8307S* S-7063
3/8200RB5T3M Qty 2 AMG/24V Qty 2 AMI-1TT3 Qty 2 P502-8304S* Qty 2 S-7061 Qty 2
50TFQ004-012

569D072-120, 576C120, 569F120