54

APPLICATION DATA — 566D150-240, 566E150-240

1. INSTALLATION — Select equipment to match or to be

slightly less than peak load. This provides better humidity

control, less unit cycling, and less part-load operation.

When selecting vapor line sizes, oil return must be evalu-

ated, particularly at part-load conditions.

The indoor fan must always be operating when outdoor unit

is operating.

Ductwork should be sized according to unit size, not build-

ing load.

To minimize the possibility of air recirculation, avoid the use

of concentric supply/return grilles.

Indoor equipment should be selected at no less than

300 cfm/ton.

OPERATING LIMITS

MINIMUM OUTDOOR-AIR OPERATING

TEMPERATURE — 566D150-240 UNITS

*Requires field-installed unloader.
MINIMUM OUTDOOR-AIR OPERATING

TEMPERATURE — 566E150-240 UNITS

LIQUID LINE DATA — 566D150-240 UNITS

NOTE:Data above is for units operating at 45 F saturated suction and
95 F entering air.

LIQUID LINE DATA — 566E150-240 UNITS

2. REFRIGERANT PIPING — It is recommended that the

refrigerant piping for all commercial split systems include a

liquid line solenoid valve, a liquid line filter drier, and a sight

glass.

For refrigerant lines longer than 75 lineal ft, a liquid line

solenoid valve and a suction accumulator are required.

Refer to the Refrigerant Specialties table.

REFRIGERANT SPECIALTIES PART NUMBERS

*Bushings required.
Maximum Outdoor 115 F
Minimum Outdoor Ambient
See Minimum Outdoor-Air
Operating Temperature
table below.
Minimum Return-Air
Temperature 55 F
Maximum Return-Air
Temperature 95 F
Normal Acceptable Saturation
Suction Temperature Range 25 to 55 F
Maximum Discharge
Temperature 295 F
Minimum Discharge Superheat 60 F
UNIT
566D
NO. OF
CYLINDERS
FULL LOAD
CAPACITY
(%)
MINIMUM
OUTDOOR-AIR
OPERATING
TEMPERATURE (F)
Base
Unit
With
Low-Ambient
Control
150
6 100 20
–20
46731
2* 33* 40
180
6 100 20
46733
2* 33* 47
240 4 100 15
25020
UNIT
566E
FULL LOAD
CAPACITY
(%)
SATURATED COND
TEMPERATURE (F)
MINIMUM
OUTDOOR-AIR
TEMPERATURE (F)
Base
Unit
With
Low-Ambient
Control
150
100/50 90 50 –20180
240
UNIT
566D
MAX
ALLOW.
LIFT
(ft)
LIQUID LINE
Max Allow.
Pressure
Drop
(psi)
Max Allow.
Temp
Loss
(°F)
150 67 72
180 82
240 87
UNIT
566E
MAX
ALLOW.
LIFT
(ft)
LIQUID LINE
Max Allow.
Pressure
Drop
(psi)
Max Allow.
Temp
Loss
(°F)
150 60 7 2
180
240
UNIT LIQUID LINE
SIZE(in.)
LIQUID LINE
SOLENOID VALVE (LLSV)
LLSV
COIL
SIGHT
GLASS
FILTER
DRIER
SUCTION LINE
ACCUMULATOR
566D150
1/2200RB7T4M AMG/24V AMI-1TT4 P502-8757S* S-7063
5/8200RA8T5M AMG/24V AMI-1TT5 P502-8757S* S-7063
566D180
1/2200RB7T4M AMG/24V AMI-1TT4 P502-8757S* S-7721
5/8200RA8T5M AMG/24V AMI-1TT5 P502-8757S* S-7721
7/8200RA8T7M AMG/24V AMI-1TT7 P502-8757S S-7721
566D240
5/8200RA9T5M AMG/24V AMI-1TT5 P502-8757S* S-7721
7/8200RA9T7M AMG/24V AMI-1TT7 P502-8757S S-7721
566E150 1/2200RB5T4M Qty 2 AMG/24V Qty 2 AMI-1TT4 Qty 2 P502-8304S Qty 2 S-7063S* Qty 2
566E180
1/2200RB5T4M Qty 2 AMG/24V Qty 2 AMI-1TT4 Qty 2 P502-8304S Qty 2 S-7063S Qty 2
5/8200RB5T5M Qty 2 AMG/24V Qty 2 AMI-1TT5 Qty 2 P502-8304S Qty 2 S-7063S Qty 2
566E240
1/2200RB6T4M Qty 2 AMG/24V Qty 2 AMI-1TT5 Qty 2 P502-8307S* S-7063S Qty 2
5/8200RB6T5M Qty 2 AMG/24V Qty 2 AMI-1TT5 Qty 2 P502-8307S* S-7063S Qty 2
50TFQ004-012

566D/E150-240