CONTROLS

OPERATING SEQUENCES

569D072-120, 576C120 — At start-up, the thermostat calls for cooling. With all safety devices satisfied, the compressor contactor and fan contactor energize, causing the compressor and outdoor-fan motor to operate. Thermostat contacts energize, allowing the field-supplied and field-installed indoor- fan contactor to function. A field-supplied and field-installed liq- uid line valve also opens, allowing the system to function in Cooling mode. As cooling demand is satisfied, the thermostat contacts break, deenergizing the contactor and causing the system to shut off. The liquid line solenoid valve closes, mini- mizing the potential for refrigerant migration. The compressor does not restart until the thermostat again calls for cooling. The system is protected with a safety circuit so that the system will not start if a fault exists (i.e., high or low pressure fault). To reset the safety circuit, set the thermostat to eliminate the cooling demand, then return to original set point. This should be done only once, and if system shuts down due to the same fault, determine the problem before attempting to restart the system.

566D150-240When the first stage of cooling thermostat closes, the timer starts. After approximately 3 seconds, the timer activates the compressor and fan motor no. 1 contactors. When the liquid pressure builds to approximately 257 psig, fan motor no. 2 is energized.

When there is demand for additional cooling capacity, the second stage of the cooling thermostat closes, energizing a field-supplied liquid line solenoid (LLS) valve, which opens. This increases the suction pressure, causing the compressor to operate at higher capacity (compressor loads).

When the fan switch is set at AUTO, the indoor-air fan cycles with the compressor. When the switch is set at CONT, the indoor-air fan runs continuously.

At shutdown, the Time Guard II timer prevents the compressor from restarting for approximately 5 minutes.

In addition, an LLS valve wired in parallel with the compressor contactor coil shuts off the liquid line to prevent refrigerant migration back to the compressor during the off cycle.

569F120 — When the thermostat calls for stage one cooling at start-up, and all safety devices are satisfied, the compressor contactor no. 1 (C1) energizes causing compressor no. 1 and outdoor-fan motor no. 1 to start (the indoor-fan contactor should be wired to start at the same time as the compressor). The liquid line solenoid (LLS) valve will open when compressor no. 1 starts, allowing refrigerant to flow in the system.

When the thermostat calls for stage two cooling, compressor contactor no. 2 (C2) energizes causing compressor no. 2 and outdoor-fan motor no. 2 to start. As the cooling demand decreases, stage two on the thermostat opens, causing compressor no. 2 and outdoor-fan motor no. 2 to shut down. As

the cooling continues to decrease, stage one of the thermostat opens causing compressor no. 1 and outdoor-fan motor no. 1 to shut down. The LLS valve for each compressor will close when the associated compressor stops, minimizing the potential for refrigerant migration during the off cycle.

The indoor-fan motor will stop if the thermostat is set to AUTO and will continue to operate if the thermostat is set to CONT. Each compressor is protected with a Cycle-LOCTMdevice so that the compressor will not operate if there is a high-pressure fault, low pressure fault, or a compressor is off due to internal line break overcurrent/overtemperature protection. To reset the Cycle-LOC device, set the thermostat higher to remove the cooling demand, then return to the original set point. This should be done only once. If the system shuts down with the same fault, the cause for the fault should be determined and corrected before the a Cycle-LOC device is reset again.

566E150-240At start-up, when the thermostat calls for first stage cooling and all safety devices are satisfied, the compres- sor contactor (C1) energizes causing compressor no. 1 and fan motor no. 1 to start. Fan motor no. 2 will start when the fan cycling pressure switch (FCPS) closes as discharge pressure builds (refer to physical data table for FCPS specifications). With the indoor-fan contactor wired to TB2-4 and TB2-9 contacts on the terminal block, the indoor fan will also start with the compressor. The liquid line solenoid (LLS) valve will open when compressor no. 1 starts, allowing refrigerant to flow in the system.

When the thermostat calls for stage two cooling, compressor contactor no. 2 (C2) energizes causing compressor no. 2 to start. As the cooling demand decreases, stage two on the thermostat opens, causing compressor no. 2 to shut down. As the cooling continues to decrease, stage one of the thermostat opens causing compressor no. 1 and outdoor-fan motor to shut down. The LLS valve for each compressor will close when the associated compressor stops, minimizing the potential for refrigerant migration during the off cycle.

The indoor-fan motor will stop if the thermostat is set to AUTO and will continue to operate if the thermostat is set on CONT. Each compressor is controlled by the thermostat so they will not start until there is a demand from the thermostat. Each compressor is protected with a Cycle-LOC device so that the compressor will not operate if there is a high-pressure fault, low-pressure fault, or compressor is off due to internal line break overcurrent/overtemperature protection. To reset the a Cycle-LOC device, set the thermostat higher to remove the cooling demand, then return to the original set point. This should be done only once. If the system shuts down with the same fault, the cause for the fault should be determined and corrected before the a Cycle-LOC device is reset again.

8

Page 8
Image 8
Bryant 569F, 576C, 569D, 566E, 566D manual Controls, Operating Sequences

569F, 566E, 566D, 569D, 576C specifications

Bryant has long been recognized for its innovative heating and cooling solutions, and the Bryant 576C, 569D, 566D, 566E, and 569F models exemplify the brand's commitment to energy efficiency, comfort, and advanced technology. Each model is designed to cater to various residential and commercial heating and cooling needs, ensuring optimal performance and reliability.

The Bryant 576C is a highly efficient air conditioning unit that offers remarkable SEER ratings, making it an eco-friendly choice for homeowners. Its advanced technology includes a variable-speed compressor, which adjusts the cooling output based on the home’s requirements, ensuring maximum comfort while minimizing energy consumption. Additionally, its Quiet operation allows for a peaceful indoor environment, as the system operates at low sound levels even during peak performance.

The Bryant 569D heating system stands out for its durability and energy efficiency. Designed with a two-stage gas valve, it provides flexible heating output, allowing for improved temperature control. This model is equipped with an ECM blower motor, ensuring quiet operation and consistent airflow. Its efficiency ratings are impressive, providing significant savings on energy bills while maintaining an ideal indoor climate.

Similarly, the Bryant 566D model emphasizes performance and reliability. Its variable-speed blower motor enhances comfort levels by providing better humidity control and even heating throughout the living space. With an emphasis on high-quality construction materials, this model ensures a long lifespan, making it a wise investment for homeowners looking for effective heating solutions.

The Bryant 566E model incorporates state-of-the-art technology, including smart thermostat compatibility, which allows users to control their heating and cooling systems remotely. This feature enhances convenience and helps to optimize energy usage based on the occupants' schedules. With its excellent design and efficiency, the 566E is perfect for those seeking a modern heating solution without compromising on comfort.

Lastly, the Bryant 569F is ideal for homeowners wanting a balance between efficiency and performance. With an ENERGY STAR certification, this model provides reliable heating while keeping energy costs low. Its compact design makes it suitable for various spaces, and the integrated safety features ensure peace of mind for users.

In summary, whether you choose the Bryant 576C, 569D, 566D, 566E, or 569F, each model reflects a commitment to quality, efficiency, and innovation, ensuring that homeowners can achieve the perfect climate in their living spaces. These heating and cooling systems leverage advanced technologies that not only provide comfort but also promote energy savings and environmental responsibility.