THIRD TEMPERATURE TEST:

10.Once the unit has run for 24 hours, perform the third temperature test.

11.Record information and calculate temperature differential in table below for the condenser/back side section under the second test.

Evaporator (Front) Side

Condenser (Back) Side

TEMPERATURE DATA FROM TESTING

Temperature / Test (time)

First (after 5 mins)

Second (after 8 hrs)

Third (after 24 hours)

Inlet Air

 

 

 

 

 

 

 

Outlet Air

 

 

 

 

 

 

 

Differential

 

 

 

(Inlet - Outlet = _; ideally 10°F - 15°F)

 

 

 

Inlet Air

 

 

 

(Ideally < 85°F)

 

 

 

 

 

 

 

Outlet Air

 

 

 

(Ideally < 120°F)

 

 

 

 

 

 

 

Differential

 

 

 

(Inlet - Outlet = _; ideally 10°F - 15°F)

 

 

 

 

 

 

 

TEMPERATURE TESTING LOCATIONS

INLET AIR -- Evaporator (Front) Side*

OUTLET AIR -- Evaporator (Front) Side*

INLET AIR -- Condenser (Back) Side*

OUTLET AIR -- Condenser (Back) Side*

*When measuring outlet air temperature on both sides of the unit (from the circular fans), hold the

thermostat at the outer edges of one of the circular fans.

Page 27

XLT 020111

Page 29
Image 29
WhisperKool XLT 6000 Temperature / Test time, Evaporator Front Side Condenser Back Side, Inlet AIR -- Condenser Back Side