Unobstructed Airflow

Unobstructed airflow to and from the unit is a critical factor in the unit’s overall performance. Make sure there is a three-foot clearance in the front of the unit, as fans blow down at an angle and should not be obstructed by racking. There should be a minimum three-foot horizontal clear- ance from the rear of the unit as well. This will assure that the unit can move the air around in an efficient manner. Avoid the attempt to camou- flage the unit by installing racking in front of the unit. This will restrict airflow and thus the unit’s ability to work efficiently.

Mounting the Unit

The unit should be mounted within 18 inches of the top of the room in order to achieve suf- ficient cooling. As the room cools down, the warm air will rise to the ceiling. Mounting the WhisperKOOL high in the room will create a consistently cool environment by capturing the warm air and replacing it with cool air. Mount- ing the unit low in the room will result in a tem- perature variation in the room due to the unit’s inability to draw warm air from the ceiling of the cellar to the unit itself.

Exhaust Room

Front of

Exhaust

WhisperKOOL

 

Intake

Wine Cellar

Door

An exterior grade (1 3/4”) door must be installed as a cellar door. It is very important that weather strip- ping is attached to all 4 sides of the door jam. A bottom “sweep” or threshold is also required. The door must have a very good seal to keep the cool cellar air from escaping out of the cellar. One of the most common problems with cooling units running continually is due to the door not sealing properly. In cases where glass doors are used and the room size is close to the recommended unit size, the next larger size WhisperKOOL should be used. This will compensate for the insulation loss due to the lower insulating rating of glass.

Page 6

XLT 020111

Page 8
Image 8
WhisperKool XLT 1600, XLT 8000, XLT 3000, XLT 4200, XLT 6000 owner manual Unobstructed Airflow, Mounting the Unit, Door