Installation

PipingLengthandElevation

Capacity

Pipe Size

Standard Length

Max.

Max.

Additional Refrigerant

(Btu/h)

 

 

m(ft)

Elevation B

Length A

g/m(oz/ft)

GAS

LIQUID

m(ft)

m(ft)

 

 

 

 

 

 

 

9k, 12k

9.52 (3/8")

6.35(1/4")

7.5 (25)

7 (23)

15 (49)

20 (0.22)

 

 

 

 

 

 

 

18k

12.7(1/2")

6.35(1/4")

7.5 (25)

7 (23)

15 (49)

20 (0.22)

 

 

 

 

 

 

 

24k

15..88(5/8")

9.52(3/8")

7.5 (25)

15 (49)

30 (98)

30 (0.33)

 

 

 

 

 

 

 

ENGLISH

Indoor unit

B

A

Outdoor unit

A

Indoor unit

Outdoor unit

Outdoor unit

Oil trap

A

 

BIndoor unit

B

If piping length is more than 5 m (16.4 ft)

Capacity is based on standard length and maximum allowance length is on the basis of reliability. Oil trap should be installed every 5~7 meters(16.4~23.0ft).