Installation

Outdoor

 

 

1. Remove the cover control from the unit by

 

 

loosening the screw.

Outdoor unit

 

Connect the wires to the terminals on the

 

Terminal block

 

control board individually as the following.

 

2. Secure the cable onto the control board with

 

 

the holder (clamper).

Over 5mm

 

3. Refix the cover control to the original position

(0.2")

Conduit panel

Power supply

 

with the screw.

 

cord

Connecting

Wiring Diagram

 

 

cable

BR BL BR BL RD

Cover control

 

 

 

ENGLISH

NOTICE

1.Separately wire power supply cord and connecting cable.

2.Use heat-proof electrical wiring capable of withstanding temperature up to 75°C(167°F).

3.Use outdoor and waterproof connection cable rated more than 300V for the connection between indoor and outdoor unit. (For example, Type SJO-WA)

Be sure to comply with local codes while running the wire from the indoor unit to the outdoor unit(size of wire and wiring method, etc).

Every wire must be connected firmly.

No wire should be allowed to touch refrigerant tubing, the compressor or any moving parts.

Installation Manual 21