Installation
FlaringWork
Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.
Cutting Tubes.
1.Use the piping kit accessory or the pipes purchased locally.
2.Measure the distance between the indoor and the outdoor unit.
3.Cut the pipes a little longer than measured distance.
4.Cut the cable 1.5m(59.1in) longer than the pipe length.
Burrs removal
1.Completely remove all burrs from the cut cross section of pipe/tube.
2.Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.
Copper |
| Slanted | Uneven Rough |
pipe | 90° | ||
|
| Pipe |
|
|
| Reamer |
Point down
ENGLISH
Putting nut on
•Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal.
(not possible to put them on after flaring work)
Flaring work
1.Firmly hold copper pipe in a Bar in the dimension shown in the table below.
2.Carry out flaring work with the flaring tool.
Outside diameter | A | |
|
|
|
mm | inch | mm |
Ø6.35 | 1/4 | 1.1~1.3 |
Ø9.52 | 3/8 | 1.5~1.7 |
Ø12.7 | 1/2 | 1.6~1.8 |
Ø15.88 | 5/8 | 1.6~1.8 |
Ø19.05 | 3/4 | 1.9~2.1 |
Flare nut
Copper tube
| "A" |
| Handle |
Bar | Bar |
| |
| Yoke | ||
|
|
| |
|
|
| Cone |
| Copper pipe |
| |
|
| Clamp handle | Red arrow mark |
|
|
|
Installation Manual 13