Installation

AirPurging

Air purging

The air and moisture remaining in the refrigerant system have undesirable effects as indicated below.

1.Pressure in the system rises.

2.Operating current rises.

3.Cooling(or heating) efficiency drops.

4.Moisture in the refrigerant circuit may freeze and block capillary tubing.

5.Water may lead to corrosion of parts in the refrigeration system.

Therefore, after evacuating the system, take a leak test for the piping and tubing between the indoor and outdoor unit.

Air purging with vacuum pump

1. Preparation

Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Note that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.

2. Leak test

Connect the manifold valve(with pressure gauges) and dry nitrogen gas cylinder to this service port with charge hoses.

Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The "Hi" knob of the manifold valve must always be kept close.

Pressurize the system to no more than 150 P.S.I.G. with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P.S.I.G. Next, test for leaks with liquid soap.

To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.

1. Do a leak test of all joints of the

 

 

 

 

tubing(both indoor and outdoor)

 

Manifold valve

and both gas and liquid side

Indoor unit

service valves.

 

 

 

 

Bubbles indicate a leak. Be sure to

 

Lo

Hi

 

 

 

 

 

wipe off the soap with a clean

 

 

 

 

cloth.

 

Charge hose

 

 

2. After the system is found to be free

Outdoor unit

 

 

 

 

 

 

 

 

 

of leaks, relieve the nitrogen

 

 

 

 

pressure by loosening the charge

 

Nitrogen gas

 

 

hose connector at the nitrogen

 

cylinder(in vertical

 

 

cylinder. When the system pressure

 

standing position)

 

 

 

 

 

 

is reduced to normal, disconnect

 

 

 

 

the hose from the cylinder.

 

 

 

 

 

 

Installation Manual

25

ENGLISH

Page 25
Image 25
LG Electronics MFL39817303 installation manual Air Purging, Air purging with vacuum pump