Power Wiring

CAUTION: The SiteGate-232 modules are Class 2 devices (less than 30 VAC). Take appropriate isolation measures when mounting a SiteGate-232 module in a control panel where Class 1 devices or wiring are present.

NOTE: Whenever possible, terminate and verify power and communication to all modules before terminating any inputs and outputs.

1.Terminate AC power at the wiring source (usually a circuit breaker or other AC source).

2.Apply power to the transformer.

3.Turn the SiteGate-232's power switch OFF (see Figure 1 for location) to prevent the module from being powered up until proper voltage is verified.

4.If you are using an internally grounded transformer, terminate the Earth Ground wire to the Gnd screw terminal as indicated in Figure 4.

CAUTION: Be sure to follow proper polarity on power connections. Note INCORRECT power wiring in Figure 5.

If the transformer is not internally grounded, terminate the two power wires as indicated in Figure 6.

5.Verify that 24 VAC is present at the power input terminals and turn the SiteGate-232's power switch on.

6.Once the power wiring procedure has been completed, the "Run" LED should turn on and begin blinking. If this does not occur, turn the power switch off and check for wiring errors.

Figure 4: SiteGate-232 module

Figure5: INCORRECT wiringofthe

Figure 6: SiteGate-232 module

powered by transformer with Earth

SiteGate-232 module powered by

powered by transformer with Floating

Ground

transformer with Earth Ground

Ground

Rev. (08-JULY-98)

6

© 1996-98 Liebert Corporation

Page 6
Image 6
Liebert user manual Power Wiring, SiteGate-232 module