Wiring and Connections

3.2Connecting Digital Inputs and Outputs

The digital inputs and outputs are found on the lower right side of the AC4’s printed wiring assembly board. This section describes how to connect devices to the AC4’s inputs and outputs.

Each input is tied to an output with the same number:

Input 1 is tied to Output 1 (default name: Device_1)

Input 2 is tied to Output 2 (default name: Device_2)

Input 3 is tied to Output 3 (default name: Device_3)

Input 4 is tied to Output 4 (default name: Device_4)

Up to four devices may be connected to the AC4. Each device must be connected to an input and an output with the same number.

To determine the proper wire size, see Table 4 - Wiring specifications.

NOTE

Each terminal block is a removable assembly to permit easier connection of more than one input or output at a time. If making multiple connections, grasp the upper portion of a block and pull firmly until the assembly pulls apart.

After making the connections, push the removed piece back into the portion attached to the printed wiring assembly until the terminal block pieces lock together.

Connecting Liebert Environmental Units

For Liebert environmental units, follow these steps (be sure to connect the same device to inputs and outputs with the same number (Input 1 and Output 1, Input 2 and Output 2, and so on):

Connect a digital input from the AC4 to the Common Alarm Relay of the environmental unit: terminals 75/76 or TB1-6,TB1-7.

Connect a digital output (numbered the same as the input) from the AC4 to the Remote Shutdown (Power Control) of the environmental unit: terminal 37/38 or TB1-4, TB1-5.

3.2.1

Connecting Digital Inputs

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUT TERMINAL

 

The four digital inputs are found on the lower right side of

 

 

 

 

 

 

 

 

 

 

 

 

BLOCKS

 

the AC4 just below the output terminal blocks, as shown at

 

 

 

 

 

 

 

 

 

 

 

 

Note numbering keys

 

right. These inputs are numbered 1 through 4.

 

 

 

 

 

 

 

 

 

 

 

 

to right of terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

blocks; outputs are

 

To connect an input:

 

 

 

 

 

 

 

 

 

 

 

 

numbered from

 

1. Turn OFF electrical power to the AC4.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

bottom (1) to top (4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. If necessary, remove a conduit knockout to permit wire

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

entry into the AC4 enclosure.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3. Bring the wire(s) into the AC4 enclosure through a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Numbering

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

conduit knockout or access slot.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

keys

 

4. Loosen the appropriate screw and slip the stripped end

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of the wire into the terminal block.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5. Tighten the screw until it holds the wire snugly.

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT TERMINAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.2.2

Connecting Digital Outputs

 

 

 

 

 

 

 

 

 

 

 

 

 

BLOCKS

 

 

 

 

 

 

 

 

 

 

 

 

 

Note numbering keys

 

The four digital outputs are found on the lower right side of

 

 

 

 

 

 

 

 

 

 

 

 

 

to right of terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

blocks; inputs are

 

the AC4 just above the input terminal blocks, as shown at

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

numbered from

 

right. These outputs are numbered 1 through 4.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

bottom (1) to top (4)

 

To connect an output:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Turn OFF electrical power to the AC4.

2.If necessary, remove a conduit knockout to permit wire entry into the AC4 enclosure.

3.Bring the wire(s) into the AC4 enclosure through a conduit knockout or access slot.

4.Loosen the appropriate screw and slip the stripped end of the wire into the terminal block.

5.Tighten the screw until it holds the wire snugly.

! CAUTION

To reduce the risk of fire or electric shock, do not interconnect the outputs of different class 2 circuits.

13

Page 19
Image 19
Liebert AC4 Connecting Digital Inputs and Outputs, Connecting Liebert Environmental Units, Connecting Digital Outputs

AC4 specifications

The Liebert AC4 is a highly advanced cooling solution designed for critical environments, such as data centers and telecommunications facilities. As data demands rise and IT equipment generates significant heat, an effective cooling system is paramount to maintaining optimal performance and reliability. The Liebert AC4 stands out in this space, offering a blend of efficiency, flexibility, and innovative technology.

One of the main features of the Liebert AC4 is its adaptability to various configurations and applications. It can be deployed in both hot aisle and cold aisle containment setups, making it versatile for different data center designs. This flexibility allows facilities to implement cooling strategies that align perfectly with their specific layouts and operational requirements.

The Liebert AC4 employs cutting-edge, variable-speed fans that enhance energy efficiency. These fans adjust their speed according to the cooling load, ensuring that the system operates at peak efficiency while significantly reducing energy consumption. This feature is essential in critical environments, where minimizing operational costs is often as important as maintaining optimal temperatures.

In addition to energy-efficient cooling, the Liebert AC4 integrates advanced monitoring and control technologies. With built-in intelligence and compatibility with the Liebert SiteScan monitoring system, users can ensure real-time visibility into their cooling operations. This monitoring capability enables data center managers to make informed decisions and swiftly address any cooling anomalies, minimizing the risk of overheating and downtime.

Furthermore, the system is designed to be easy to install and maintain, reducing downtime during setup and upkeep. The modular design allows for scalability, enabling organizations to expand their cooling capabilities as their needs grow.

The Liebert AC4 also features a robust construction that enhances reliability and durability, making it an ideal choice for environments where equipment uptime is critical. Its streamlined design not only optimizes airflow and cooling distribution but also contributes to aesthetic considerations in professional settings.

In conclusion, the Liebert AC4 combines efficiency, versatility, and advanced technologies to deliver a reliable cooling solution for modern data centers and critical facilities. Its variable-speed fans, flexible configurations, and advanced monitoring capabilities position it as a leader in the competitive field of cooling solutions, ensuring that critical equipment remains operational and efficient. Organizations looking to enhance their cooling strategies will find the Liebert AC4 to be an invaluable asset in today’s fast-paced digital landscape.