System and Control Options

7.8.4 Specify Hold Delay Time

Setup Operation Menu

 

After an output changes state, the hold delay timer directs the AC4 to ignore all inputs in the same zone for the specified time.

This delay is the amount of time that must elapse before the AC4 acknowledges a change of state in any input. The default is 10 minutes (displayed as 10 MIN : 00 SEC).

The time delay applies only when a monitored output device changes from its normal state—for example, the AC4 detects a closed contact that is defined as Normally Open.

When the output device returns to its normal state, the AC4 acknowl- edges any input change of state immediately.

The hold delay timer also takes effect when the AC4 is powered up. All alarms are ignored until the hold delay time expires.

AUTO SEQUENCING OFF STANDBY TESTING OFF FAILED STANDBY N ↑↓ =NEXT =SELECT

> HOLD DELAY : 10:00

RESTART

: 00:06

Hold Delay Time

HOLD DELAY

10 MIN : 00 SEC ↑↓ =NEXT =EDIT

From the Setup Operation Menu, choose Hold Delay, as shown at right, and press Enter .

To change the time delay in minutes and seconds (in the range of 00:00 to 99:59):

For minutes (MIN), press and hold one of the arrow keys ↑↓

Press Enter to advance to seconds (SEC).

For seconds (SEC), press and hold one of the arrow keys ↑↓

When finished, press Enter again.

7.8.5Specify Restart Time

scroll through the numbers 00-99.

scroll through the numbers 00-59.

Setup Operation Menu

The restart delay timer directs the AC4 to wait a specified time before

 

 

 

 

AUTO SEQUENCING OFF

changing the state of an output. This feature can prevent needless

 

STANDBY TESTING OFF

responses to transient conditions.

 

FAILED STANDBY N

If two or more outputs change state simultaneously, the AC4 begins a

 

↑↓ =NEXT

=SELECT

 

HOLD DELAY

: 10:00

 

new countdown between each output change of state.

> RESTART

 

: 00:06

 

The default is 6 seconds (displayed as 00 MIN : 06 SEC).

• From the Setup Operation Menu, choose Restart, as shown at

Restart Delay Time

RESTART DELAY

right, and press Enter .

00

MIN : 06 SEC

• To change the time delay in minutes and seconds (in the range of

↑↓

=NEXT =EDIT

00:00 to 99:59):

 

• For minutes (MIN), press and hold one of the arrow keys ↑↓

 

 

scroll through the numbers 00-99.

 

 

• Press Enter

to advance to seconds (SEC).

 

 

• For seconds (SEC), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-59.

• When finished, press Enter again.

45

Page 51
Image 51
Liebert AC4 user manual Specify Hold Delay Time, Specify Restart Time, Setup Operation Menu, Restart Delay Time

AC4 specifications

The Liebert AC4 is a highly advanced cooling solution designed for critical environments, such as data centers and telecommunications facilities. As data demands rise and IT equipment generates significant heat, an effective cooling system is paramount to maintaining optimal performance and reliability. The Liebert AC4 stands out in this space, offering a blend of efficiency, flexibility, and innovative technology.

One of the main features of the Liebert AC4 is its adaptability to various configurations and applications. It can be deployed in both hot aisle and cold aisle containment setups, making it versatile for different data center designs. This flexibility allows facilities to implement cooling strategies that align perfectly with their specific layouts and operational requirements.

The Liebert AC4 employs cutting-edge, variable-speed fans that enhance energy efficiency. These fans adjust their speed according to the cooling load, ensuring that the system operates at peak efficiency while significantly reducing energy consumption. This feature is essential in critical environments, where minimizing operational costs is often as important as maintaining optimal temperatures.

In addition to energy-efficient cooling, the Liebert AC4 integrates advanced monitoring and control technologies. With built-in intelligence and compatibility with the Liebert SiteScan monitoring system, users can ensure real-time visibility into their cooling operations. This monitoring capability enables data center managers to make informed decisions and swiftly address any cooling anomalies, minimizing the risk of overheating and downtime.

Furthermore, the system is designed to be easy to install and maintain, reducing downtime during setup and upkeep. The modular design allows for scalability, enabling organizations to expand their cooling capabilities as their needs grow.

The Liebert AC4 also features a robust construction that enhances reliability and durability, making it an ideal choice for environments where equipment uptime is critical. Its streamlined design not only optimizes airflow and cooling distribution but also contributes to aesthetic considerations in professional settings.

In conclusion, the Liebert AC4 combines efficiency, versatility, and advanced technologies to deliver a reliable cooling solution for modern data centers and critical facilities. Its variable-speed fans, flexible configurations, and advanced monitoring capabilities position it as a leader in the competitive field of cooling solutions, ensuring that critical equipment remains operational and efficient. Organizations looking to enhance their cooling strategies will find the Liebert AC4 to be an invaluable asset in today’s fast-paced digital landscape.