System and Control Options

7.3.4Set Up Alarmable Inputs in Latched or Unlatched Mode

Alarmable input points may be set up in Latched mode (Y), which requires the user to clear the AC4 alarms after an alarm has occurred, or Unlatched mode (N), in which alarms will automatically clear after a return-to-normal state. The default setting for alarmable inputs is Y (Latched). Any input defined as an event is automatically Unlatched.

An input defined as Latched does not reset automatically after an alarm. It will remain in the triggered position even after the moni- tored device returns to normal. After an alarm, the user must manu- ally reset Latched inputs, as described in 7.10.1 - Clear Active Alarms. This also means that any outputs linked to a Latched digital input will remain triggered until the input is manually reset.

An input defined as Unlatched will automatically track the status of the monitored device. No action by the user is required.

From the Setup Inputs Menu, choose Latched, as shown above right, and press Enter .

• To change this feature, use the arrows ↑↓ to choose Y (Yes - Latched) or N (No - Unlatched), then press Enter .

NOTE: Only alarmable input points may be set up as Latched. If you attempt to set up an event as Latched, the message shown at right appears. Press the ESC key to return to the previous screen to con- tinue configuring the digital input.

The only way to reset latched alarms is by clearing active alarms. This step is required to return latched points to their normal state. For details, see 7.10.1 - Clear Active Alarms.

7.3.5Set Up Delay Time

Each input may be set up with a specified time delay between the occurrence of an alarm or event—a monitored device changes state— and any response by the AC4. This feature can prevent needless responses to transient conditions.

This delay is the amount of time that must elapse before the AC4 acknowledges the change of state in the monitored device and takes any further action, such as dialing configured pagers. The default time delay is 1 second (displayed as 00 MIN : 01 SEC).

The time delay applies only when a monitored device changes from its normal state—for example, the AC4 detects a closed contact that is defined as Normally Open.

When the monitored device returns to its normal state, the AC4 acknowledges the change of state after the delay timer ends its countdown.

Setup Inputs Menu

SETUP DEVICE_1

LABEL: DEVICE_1

NORM OPEN/CLOSE: NO

ALARM/EVENT: AL

↑↓ =NEXT

=SELECT

>LATCHED: N

DELAY: 00:01

Latched / Unlatched

IS ALARM

LATCHED? N

↑↓ =Y/N

=END

Message (if input has been defined as an event)

LATCH NOT ALLOWED WHEN IN EVENT MODE

ESC=BACK

Setup Inputs Menu

SETUP DEVICE_1

LABEL: DEVICE_1

NORM OPEN/CLOSE: NO

ALARM/EVENT: AL

↑↓ =NEXT

=SELECT

LATCHED: N

DELAY: 00:01

Delay Time

DELAY TIME BEFORE TRIGGER?

00 MIN : 01 SEC ↑↓ =SELECT =NEXT/END

From the Setup Inputs Menu, choose Delay, as shown at right, and press Enter .

To change the time delay in minutes and seconds (in the range of 00:00 to 99:59):

• For minutes (MIN), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-99.

• Press Enter to advance to seconds (SEC).

• For seconds (SEC), press and hold one of the arrow keys ↑↓ scroll through the numbers 00-59.

• When finished, press Enter again.

30

Page 36
Image 36
Liebert AC4 user manual Set Up Alarmable Inputs in Latched or Unlatched Mode, Set Up Delay Time, Latched / Unlatched

AC4 specifications

The Liebert AC4 is a highly advanced cooling solution designed for critical environments, such as data centers and telecommunications facilities. As data demands rise and IT equipment generates significant heat, an effective cooling system is paramount to maintaining optimal performance and reliability. The Liebert AC4 stands out in this space, offering a blend of efficiency, flexibility, and innovative technology.

One of the main features of the Liebert AC4 is its adaptability to various configurations and applications. It can be deployed in both hot aisle and cold aisle containment setups, making it versatile for different data center designs. This flexibility allows facilities to implement cooling strategies that align perfectly with their specific layouts and operational requirements.

The Liebert AC4 employs cutting-edge, variable-speed fans that enhance energy efficiency. These fans adjust their speed according to the cooling load, ensuring that the system operates at peak efficiency while significantly reducing energy consumption. This feature is essential in critical environments, where minimizing operational costs is often as important as maintaining optimal temperatures.

In addition to energy-efficient cooling, the Liebert AC4 integrates advanced monitoring and control technologies. With built-in intelligence and compatibility with the Liebert SiteScan monitoring system, users can ensure real-time visibility into their cooling operations. This monitoring capability enables data center managers to make informed decisions and swiftly address any cooling anomalies, minimizing the risk of overheating and downtime.

Furthermore, the system is designed to be easy to install and maintain, reducing downtime during setup and upkeep. The modular design allows for scalability, enabling organizations to expand their cooling capabilities as their needs grow.

The Liebert AC4 also features a robust construction that enhances reliability and durability, making it an ideal choice for environments where equipment uptime is critical. Its streamlined design not only optimizes airflow and cooling distribution but also contributes to aesthetic considerations in professional settings.

In conclusion, the Liebert AC4 combines efficiency, versatility, and advanced technologies to deliver a reliable cooling solution for modern data centers and critical facilities. Its variable-speed fans, flexible configurations, and advanced monitoring capabilities position it as a leader in the competitive field of cooling solutions, ensuring that critical equipment remains operational and efficient. Organizations looking to enhance their cooling strategies will find the Liebert AC4 to be an invaluable asset in today’s fast-paced digital landscape.