Liebert GXT2-6000RTL630 user manual Specifications, UPS specifications

Models: GXT2-6000RTL630

1 44
Download 44 pages 17.9 Kb
Page 40
Image 40

Specifications

13.0SPECIFICATIONS

Table 6

UPS specifications

 

 

 

Model Number

GXT2-6000RTL630

 

 

 

 

Model Rating

6000VA/4200W

 

 

Dimensions, in. (mm)

 

 

Unit, W x D x H

8.7 x 21.5 x 16.9 (221 x 547 x 430)

 

 

 

 

Shipping, W x D x H

22.0 x 27.2 x 19.7 (560 x 690 x 500)

 

 

Weight, lb (kg)

 

 

Unit

57.2 (26)

 

 

 

 

Shipping

81.5 (37)

 

 

Input AC Parameters

 

 

Nominal Operating Frequency

50 or 60Hz (Factory Default = 60)

 

 

 

 

Factory Default VAC

208VAC

 

 

 

 

User Configurable VAC

208/220/230/240VAC

 

(May be modified using configuration program)

 

 

Operating Voltage Range Without

176 – 276VAC

 

Battery Operation

 

 

 

Maximum Allowable VAC

276VAC

 

 

Input Frequency Without Battery

40 - 70Hz

 

Operation

 

 

 

Input Power Connection

L6-30P Plug (on PD-L630 power distribution box)

 

 

Output AC Parameters

 

 

Factory Default VAC

208VAC

 

 

 

 

Output Connections

(2) L6-20R and (2) L6-30R on 12" (300mm) cords

 

(on PD-L630 power distribution box)

 

 

 

Frequency

50Hz or 60Hz, Nominal

 

 

 

 

Waveform

Sinewave

 

 

 

 

Main Mode

>200% for 96 milliseconds; 131 - 199% for 2 seconds;

 

Overload

112- 129% for 10 seconds with transfer to bypass

Bypass Protection Limits

 

 

Disable Bypass operation

If input voltage exceeds ±15% of the nominal voltage

 

 

 

 

Re-enable Bypass operation

If input voltage returns to within ±10% of nominal output voltage

 

 

 

 

Disable Bypass operation

When the input frequency prevents synchronous operation

 

 

Environmental

 

 

Operating Temperature

32°F to 104° F (0°C to 40°C)

 

 

 

 

Storage Temperature

5°F to 122° F (-15°C to 50°C)

 

 

 

 

Relative Humidity

0-95% non-condensing

 

 

 

 

Operating Elevation

Up to 6600 ft (2000m) at 104°F (40°C) without derating

 

Storage Elevation

50,000 ft. (15,000m) maximum

 

 

 

 

Audible Noise

<55 dBA, at 3 ft. (1m) from the rear

 

<50 dBA, at 3 ft. (1m) from the front or sides

 

 

Agency

 

 

Safety

UL, C-UL Listed to UL1778

 

 

 

 

EMI/EMC

FCC Class B

 

 

 

 

ESD

EN61000-4-2, Level 4, Criteria A

 

 

 

 

Radiated Susceptibility

EN61000-4-3, Level 3, Criteria A

 

 

 

 

Electrical Fast Transient

EN61000-4-4, Level 4, Criteria A

 

 

 

 

Surge Immunity

EN61000-4-5, Level 3, Criteria A

 

 

 

 

Transportation

ISTA Procedure 1B

 

 

 

36