Troubleshooting

Table 5

Battery run times

 

 

 

 

 

 

 

Load%

6000VA

 

 

10%

94

 

 

20%

46

 

 

30%

29

 

 

40%

21

Internal Battery

50%

17

(minutes)

 

60%

13

 

 

70%

11

 

 

80%

9

 

 

90%

8

 

 

100%

7

 

 

10%

222

 

 

20%

124

 

 

30%

81

Internal Battery

40%

60

50%

49

+ 1 External Battery

60%

39

Cabinet (minutes)

70%

33

 

 

 

 

80%

28

 

 

90%

24

 

 

100%

21

 

 

10%

350

 

 

20%

197

 

 

30%

135

Internal Battery

40%

105

50%

85

+ 2 External Battery

60%

70

Cabinets (minutes)

70%

58

 

 

 

 

80%

50

 

 

90%

43

 

 

100%

38

 

 

10%

478

 

 

20%

269

 

 

30%

185

Internal Battery

40%

145

50%

123

+ 3 External Battery

60%

101

Cabinets (minutes)

70%

85

 

 

 

 

80%

73

 

 

90%

63

 

 

100%

55

 

 

10%

606

 

 

20%

341

 

 

30%

235

Internal Battery

40%

184

50%

156

+ 4 External Battery

60%

131

Cabinets (minutes)

70%

113

 

 

 

 

80%

97

 

 

90%

85

 

 

100%

75

Using the configuration program, the user may specify the number of GXT2-240VBATTUL external battery cabinets attached to the UPS. The factory default is programmed for internal batteries only.

Table 5 above shows the estimated run times at different loads.

34

Page 38
Image 38
Liebert GXT2-6000RTL630 user manual Battery run times