Battery Run Times

Battery Run Times

Load %

6kVA

6kVA + (1)

6kVA + (2)

 

 

GXT240VBATT

GXT240VBATT

10%

69

250

360

20%

58

197

301

25%

52

174

278

30%

48

155

248

40%

33

117

190

50%

23

88

140

60%

17

73

110

70%

14

60

94

75%

12

54

85

80%

11

50

77

90%

9

42

68

100%

8

37

59

 

 

 

 

Load %

10kVA

10kVA + (1)

10kVA + (2)

 

 

GXT240VLRT

GXT240VLRT

10%

71

480

900

20%

60

390

730

25%

55

345

655

30%

49

305

585

40%

39

230

450

50%

29

164

335

60%

23

129

265

70%

20

105

225

75%

18

93

205

80%

17

85

190

90%

14

70

155

100%

12

60

125

Note: All run times are in minutes, assume fully charged batteries, and are typical at 25OC (77OF) with resistive loads.