Liebert GXTTM Installation Instructions, Installation Considerations, Inspection, Location

Models: GXTTM

1 30
Download 30 pages 64 Kb
Page 18
Image 18
INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS

These instructions are for use by competent personnel only.

INSTALLATION CONSIDERATIONS

Detailed instructions to help you install the UPS are provided in the following pages; however, you should give some consideration to the proposed environment in which the UPS is to be installed, and carry out some preparatory work.

INSPECTION

Before you install the UPS, give it a thorough visual examination to ensure it has not been subjected to shipping damage. If it is not in perfect condition, you should advise both the shipper and the supplier immediately. DO NOT ATTTEMPT TO INSTALL A DAMAGED UPS.

Check the UPS rating plate that the UPS is suitable for operation on your mains voltage and load voltage requirements.

Before disposing of the UPS packaging, check that you have removed to a safe place the user manual and any other items shipped with the unit to be used in its installation.

CAUTION:

GXT6000 UPS weighs up to 139kg - GXT10000 UPS weighs up to 244kg. Use adequate handling aids when moving or installing the UPS. The UPS is fitted with castor wheels for easy movement. Take care when the UPS is removed from its packing and being wheeled across an uneven floor without the stabilisers fitted, that it does not tip over. See notes on adjustment of levelling feet and stablisers.

LOCATION

Locate the UPStation GXT indoors in a controlled environment, where it cannot be accidentally disconnected. Locate it in an area with unrestricted airflow, away from water, flammable liquids, gases, corrosives, or conductive contaminants.

Give consideration to the airflow requirements- (see below)- and allow at least 150mm (6inches) free space around the UPS, with a minimum of 300mm (12inches) at the back to enable easy operator access to the rear panel mounted input/output/battery circuit breakers.

Air vents are located at the front and the rear of the UPS. Do not position the UPS in an enclosed space where airflow is restricted.

Optional battery cabinets are designed to be placed on either side of the UPS.

Electrical maintenance/servicing requires access to both sides of the UPS, provide the necessary free space or use a flexible wiring system to allow the UPS to be pulled forward.

Maintain an ambient temperature range of 0 - +40° centigrade (32-104° F) NOTE- UPS operation in temperatures above 25°C (77°F) reduces battery life.

16

Page 18
Image 18
Liebert GXTTM Installation Instructions, These instructions are for use by competent personnel only, Inspection, Location