Installation

2.3.2Connecting to External Panel Boards

The following instructions are also shipped attached to the rear of the unit.

INPUT CABLING AND PROTECTION

Table Below Applies to 4-16kVA Scalable Systems:

Stand-alone UPS or

UPS equipped with a Maintenance Bypass Cabinet (Without Transformer)

 

Input Voltage – 208VAC

Input Voltage – 240VAC

 

Max. Current

Recommended

Max. Current

Recommended

Max. System

Input Protection

Input Protection

in UPS mode

in UPS mode

Load Rating

Circuit Breaker

Circuit Breaker

 

 

4kVA

18 amps

50 amps

15 amps

50 amps

8kVA

36 amps

50 amps

31 amps

50 amps

 

 

 

 

 

12kVA

53 amps

75 amps

46 amps

75 amps

 

 

 

 

 

16kVA

70 amps

100 amps

62 amps

100 amps

 

 

 

 

 

Terminal

 

Maximum: 35mm2 (2AWG)

 

Block

 

Minimum: 16mm2 (6AWG)

 

Details

 

Torque Rating: 2.5-3.0Nm (22-26in/lbs)

 

UPS With Maintenance Bypass Cabinet (With Transformer)

Single Input Feed: All UPS ratings must use 100A input circuit breaker protection.

Dual Input Feed: See table below.

 

 

 

UPS Feed

 

Bypass Feed

 

 

 

 

 

 

Input Voltage – 208VAC

Input Voltage – 240VAC

208V or 240V

 

 

 

 

 

 

 

 

Max. Current

Recommended

Max. Current

 

Recommended Input

Recommended

Max. System

in UPS mode

Input Protection

in UPS mode

 

Protection Circuit Breaker

Input Protection

Load Rating

 

Circuit Breaker

 

 

 

Circuit Breaker

4kVA

18 amps

50 amps

15 amps

 

50 amps

100 amps

8kVA

36 amps

50 amps

31 amps

 

50 amps

100 amps

 

 

 

 

 

 

 

12kVA

53 amps

75 amps

46 amps

 

75 amps

100 amps

 

 

 

 

 

 

 

16kVA

70 amps

100 amps

62 amps

 

100 amps

100 amps

 

 

 

 

 

 

Terminal

 

 

Maximum: 35mm2 (2AWG)

 

Block

 

 

Minimum: 16mm2 (6AWG)

 

Details

 

Torque Rating: 2.5-3.0Nm (22-26in/lbs)

 

 

 

Bypass Voltage Jumper Position (TB2)

 

 

 

 

 

 

Bypass Voltage Selection

208 VAC

240 VAC

(Factory Default)

(Field Change)

 

 

 

Jumper/link on upper two screws

Jumper/link on lower two screws