Installation

2.3.3REPO Connection

The Nfinity is equipped with a Remote Emergency Power Off (REPO) connection.

NOTE

A jumper is factory installed between pins 1 & 2 to disable the Control Switch (SW2). This will prevent the unit from being started during installation. This jumper must be removed in order to start the unit.

Figure 2 REPO switch connections

Hanger for cable-tie to strain relief REPO wiring

REPO switch on rear of unit

REPO jumper

REPO connections

REPO connections

 

connected

 

for normally open

for normally closed

 

as shipped

switch system

switch system (fail-safe)

1

2

3

4

1

2

3

4

1

2

3

4

NOTE

Remove jumper before wiring.

If the installation does not require connection to a REPO system, the jumper must be removed.

Key to REPO switch connections

1.24 V DC, 50mA

2.Sense

3.Sense

4.Ground

! CAUTION

To maintain safety, Signal Edge Low Voltage (SELV) barriers, and electromagnetic compatibility, signal cables should be segregated and run separately from power cables.