Operating Instructions

Change Configuration Settings - Change Settings Menu

Starting from the Main Menu, locate and press UPS Configuration. From the UPS Configuration screen, select the Change Settings option. You may configure Nfinity from a large variety of selec- tions. Items indicated by an asterisk (*) are the selected settings.

Main Menu

UPS Status

>UPS Configuration Display Date/Time Event Log Active Alarms Transfer to Bypass Module Replacement Service Tools

UPS Configuration

UPS Configuration

Review Settings

>Change Settings Service Mode

Change Settings

Input Voltage

Display Voltage

Frequency Sync Range

Frequency Slew Rate

Set Password

Auto Battery Test

Low Battery Warning

Auto Restart

User Settings

Set Date/Time

Max Load Alarm Set

UPS Shutdown Delay

Redund Alarm Set

Service Contact

Remote Shutdown

External Battery

Bypass Alarm Mode

Intelli-Batt Ca.

Air Filter Reminder

Guarantee Shutdown

Line Compensation

Factory Defaults

Input Voltage: Select the required input voltage set- ting. This voltage must match the bypass voltage jumper setting.

Input Voltage

*208/120

240/120

Display Voltage: Displays the actual voltage the unit is configured for.

Display Voltage 208

* 240

Frequency Sync Range: Sets the window to which the system synchronizes to the input supply.

Frequency Sync Range

0.5Hz

1.0Hz

2.0Hz

3.0Hz

4.0Hz

*5.0 Hz

Frequency Slew Rate: Sets the rate of change of frequency through the sync range window.

Frequency Slew Rate

0.5Hz

1.0Hz

2.0Hz

3.0Hz

4.0Hz

*5.0 Hz

Set Password: Set a Password to prevent unauthorized users from changing the configuration of the Nfinity. It can be up to seven characters in length. Once set, the password will be required to change the configuration.

Set Password xxxxxxx

NOTE

If the password is lost, call Liebert Technical Support.

23