Piping
Figure 22 Profile view of the Liebert XD system
Return Line
Service
Valve
Supply
Line
7.Place the protective dust cap and plug back onto both ends of the couplers on the Liebert XDH and the port pipe.
Figure 23 Piping mains without Liebert XDH and Liebert XD Flex Pipe
8.Repeat Steps 5 through 7 for the return couplers (larger couplers).
9.Carefully lay the Liebert XD Flex Pipe aside.
CAUTION
! Risk of tubing kinks. Can cause permanent damage to the Liebert XD Flex Pipes. Do not fold or bend Liebert XD Flex Pipe.
5.11 Insulation
To minimize the possibility of condensation, insulate all piping between the Liebert XDH and the Lie- bert XDP or Liebert XDC.
22