Electrical
6.0ELECTRICAL
The unit must be installed in accordance with national wiring regulations. Refer to the unit’s serial tag for electrical requirements. Refer to Table 3 for details.
WARNING
! Risk of electric shock. Can cause death or injury.
Disconnect both electric power cords before working within the unit.
6.1 Connecting High Voltage Wiring
The Liebert XDH requires
The XDH will function properly with only one power cord. The second power cord permits connection to a separate power source to increase
To attach the power cords, clip the plastic hangers attaching the cords to the Liebert XDH. Press the appropriate end of each cord onto the electrical inlet. Attach the
Figure 24 Liebert XDH electrical connections
60Hz MODELS ONLY Field wiring connections at terminal strip to be NEC Class 2. Use switch contacts with 75VA minimum rating.
50Hz MODELS ONLY Field wiring connections
at terminal strip for safety extra low voltage circuits only. Use switch contacts rated 75VA minimum, 24VAC maximum.
Condensate Detection
Dry
Connections
(Upper Circuit 84, 85)
Condensate Detection
Dry
Connections
(Lower Circuit 82, 83)
IEC Primary Power Inlet
IEC Secondary Power Inlet
Rear of Liebert XDH | Power Cord Strain Relievers |
Panel Removed for Clarity |
23