General product information
3.0GENERAL PRODUCT INFORMATION
3.1Product/System Description
The Liebert XDH is designed for placement within a row of computer cabinets in the data center in a
Chilled
Replaceable front panels on the Liebert XDH may be customized to match the appearance of various computer manufacturer’s equipment, allowing the Liebert XDH to blend in with adjacent server equipment and enclosures. Air diffusers are available to direct cooling air for more efficient cooling, depending on the Liebert XDH’s positioning in a row or at the end of a row.
The Liebert XDH is not expected to produce any condensation because of its location, usually in the data center. A condensate pan is provided as a precaution. It does not have a drain fitting or other means of being emptied.
A Liebert
The complete cooling system consists of Liebert XDH modules, Liebert XDP or Liebert XDC pumped refrigerant distribution units, power and signal cabling and interconnecting piping, see Figure 3 below.
Figure 3 Liebert XDH hydraulic schematic
Liebert XDC
or
Liebert XDP
Liebert XDC
or
Liebert XDP
Pumped
Refrigerant
Pumped
Refrigerant
XD Cooling
Module *
XD Cooling
Module *
XD Cooling
Module *
XD Cooling
Module *
Supply Lines
(2 per unit)
Return Lines
(2 per unit)
*XDCF, XDH, XDO or XDV
3.2Checking and Unpacking
When the Liebert XDH is delivered, inspect all items for either visible or concealed damage. Damage should be immediately reported to the carrier and a damage claim filed with a copy sent to Liebert or to your sales representative. If you later find any concealed damage, report it to the shipping company and your local Liebert representative.
Check to be sure all required assemblies and parts have been received.
The Liebert XDH is shipped in protective packaging and secured to a pallet (see Figure 5). Do not remove these protective items from the Liebert XDH before it is at the installation location. When unpacking and handling the Liebert XDH, exercise extra care to prevent damage.
4