Outside Weatherhoods

The weatherhoods must have built-in “bird” screen with 1/4 in (6.35 mm) minimum mesh to prevent birds and rodents from entering into the ductwork. Do not use smaller mesh as it will be very susceptible to plugging up. Gravity dampers at the vents must not be used as they will restrict air flow and often “seize up”. The pre- ferred location of the outside weatherhoods is:

no less than 10 ft. (3 m) apart from each other

at least 18 in ( 46 cm) above snow line or ground level

away from sources of contaminants, such as automobile exhaust fumes, gas meters, garbage cans, containers, etc.

not exposed to prevailing winds, whenever reasonable possible

The outside perimeter of the weatherhood must be caulked to prevent leakage into the building.

The design and size of the weatherhoods or louvres chosen by the installer must allow for adequate free area. Water and snow penetration of the system is mini- mized when the airflow does not exceed 1000 FPM (5.08 m/s) free area velocity.

Ducting from the

Weatherhoods

Galvanized sheet metal ducting with sufficient cross sec- tion with an integral single piece vapour barrier should be used to connect the HRV to the weatherhoods. All duct- ing must meet UL Class 1 requirements.

A minimum R value of insulation should be equal to 4 (RSI 0.75)

A good bead of high quality caulking (preferably acousti- cal sealant) and taping with a high quality aluminum foil tape is recommended to seal the duct to both the HRV and the weatherhood.

Warmside Ducting - General

Ducting from the HRV to the different areas in the build- ing should be galvanized metal whenever possible.

To minimize airflow losses in the ductwork system, all ducts should be as short as possible and with as few- bends or elbows as possible. 45° elbows are preferred to 90° elbows. Use “Wye” (Y) fittings instead of “Tees”

(T) whenever possible.

All duct joints must be fastened with screws, rivets or duct sealant and wrapped with a quality duct tape to pre- vent leakage. We recommend aluminum foil tape.

Stale Air Return System

The stale air return system is used to draw air from the points in the building where the worst air quality prob- lems occur. Balancing dampers and/or adjustable grilles are recommended on all return air lines which are used during installation to help balance the “draw” from different areas of the building.

Alternately, the stale air may be drawn directly from the return air duct. When this system is used, the air han- dler’s blower must constantly operate. The exhaust takeoff connection must be at least a 3 ft (1 m) from a directly connected HRV supply duct if both are con- nected to the same duct run. Static pressure of the air handlers return system should be noted and compen- sated for if, it is apparent that the static pressure of the return in the air handler will exceed .1 to .15” W.C.

A damper located just prior to the HRV is required to balance the stale air exhausted with the fresh air sup- ply entering the building.

Return air suction points should be located on the opposite side of the room from the fresh air inlet. The inlets may be located in the ceiling or high on the walls and fitted with inlet grilles.

Many commercial activities produce air contaminants in the form of dusts, fumes, mists, vapours and gases. Contaminants should be controlled at the source so that they are not dispersed through the building nor allowed to increase to toxic concentration levels. The ventilator allows for economical operation of the HVAC system while effectively removing contaminants from the space.

In designing the exhaust portion of the system the exhaust grilles are placed so as to remove the contami- nants while not allowing them to enter the breathing zone of the occupants.

For contaminants that are lighter than air, grilles should be located high on the wall. If contaminants are heavier than air, a lower placement of the grilles will be required. Information on a contaminants specific gravity and toxicity should be available from chemical data sheets.

13

Page 13
Image 13
Lifebreath 1200DDPOOL Outside Weatherhoods, Ducting from Weatherhoods, Warmside Ducting General, Stale Air Return System

1200DDPOOL, 700DDPOOL, 1000RHCAC, 1000RHC specifications

Lifebreath is a brand renowned for its commitment to energy-efficient indoor air quality solutions. Among their offerings, the Lifebreath 700DDPOOL, 1200DDPOOL, 1000RHCAC, and 1000RHC stand out as exemplary products designed for various residential and commercial settings. These units leverage cutting-edge technologies to provide superior ventilation, heat recovery, and air quality management.

The Lifebreath 700DDPOOL is specifically designed for indoor pools and similar environments. This model boasts dual-flow ventilation, which simultaneously circulates fresh air into the space while expelling stale air. The 700DDPOOL features a built-in dehumidistat, ensuring optimal humidity levels are maintained, which is vital for preventing mold and preserving air quality. Its energy recovery capabilities make it an eco-friendly choice, reclaiming heat from exhaust air to pre-condition incoming air, thus significantly reducing heating costs.

The Lifebreath 1200DDPOOL offers similar benefits but on a larger scale. With a higher airflow capacity, the 1200DDPOOL is ideal for larger pool areas or heavily used commercial spaces. It also incorporates advanced filtration technologies that trap allergens, dust, and pollutants, resulting in cleaner air. Both the 700DDPOOL and 1200DDPOOL are engineered for easy installation and maintenance, with features like removable filters and accessible components.

The Lifebreath 1000RHCAC and 1000RHC models shift focus towards whole-home ventilation and air conditioning solutions. The 1000RHCAC combines heat recovery with air conditioning capabilities, allowing for year-round climate control. The unit’s heat exchanger efficiently recovers heat from the outgoing air and transfers it to the incoming air, ensuring that energy is conserved even during cooling seasons.

In contrast, the Lifebreath 1000RHC emphasizes effective heat recovery without an integrated air conditioning system, making it an excellent choice for areas where cooling is not a priority. Both models boast a quiet operation, ensuring no disruption to daily living, along with energy-efficient certifications that appeal to eco-conscious consumers.

Overall, Lifebreath’s 700DDPOOL, 1200DDPOOL, 1000RHCAC, and 1000RHC models provide exceptional performance, versatility, and user-friendly features. These air management systems represent the future of sustainable indoor air quality solutions, meeting diverse ventilation needs while prioritizing energy efficiency and comfort. With Lifebreath, users can breathe easier knowing they have invested in cutting-edge technology designed for health and efficiency.