![Model 500DCS](/images/new-backgrounds/44665/4466511x1.webp)
Model 500DCS
SPECIFICATIONS
CORES
Modular (4 section) patented aluminum heat recovery cores arranged for high efficiency crossflow ventilation.
MOTORS
Two PSC, 5 speed double shafted, 120 VAC, 3.15 Amps each (6.3 total on high speed). HP - 1/10, 1625 RPM. Watts - total on High Speed - 610.
FILTERS
Washable air filters in exhaust and supply air streams.
BLOWERS
Centrifugal type rated at 530 cfm (250 L/s) free air delivery. Each air stream has two centrifugal blowers driven by two PSC motors.
CONNECTION DUCT SIZES
AIRFLOW L/s (CFM)
282(600)
235(500)
190(400)
143(300)
94(200)
42(100)
PERFORMANCE
AIRFLOWS (Each Air Stream)SPEED 5
4
3
2
1
25 | (.1) | 50 | (.2) | 75 | (.3) | 100 | (.4) | 125 | (.5) |
EXTERNAL STATIC PRESSURE IN PASCALS (in. W.C.)
6.3HIGH
3.8MED
3.1LOW
TOTAL CURRENT DRAW (AMPS) @ 120 VAC
Four - 14" x 8" (356 mm x 200 mm).
MOUNTING
Unit to be set on support brackets hung by threaded rod type apparatus (brackets and rods not included).
CASE
20 gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated with foil faced insulation duct liner where required to prevent exterior condensation. Drain connection, One - 1/2" (12 mm) O.D. CONTROLS ControlAir 15
DEFROST
Supply bypass damper routes indoor air to defrost cores.
WEIGHT 178 lbs. (81 kg) SHIPPING WEIGHT 203 lbs. (92 kg)
TEMPERATURE EFFECTIVENESS
EFFECTIVENESS | 100% |
| 90% |
| 80% |
NOTE: Exhaust Relative Humidity (RH) at 40%
94 | 143 | 190 | 235 | 282 |
(200) | (300) | (400) | (500) | (600) |
AIRFLOW IN L/s (CFM)
|
|
|
| inches (mm) |
|
| ||
EXHAUST AIR |
| EXHAUST AIR |
|
|
|
|
|
|
| FROM BUILDING |
|
|
| MOUNTING POINTS |
| ||
TO OUTSIDE |
|
|
|
|
| |||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| 150 mm |
|
|
|
|
|
| 150 mm |
| (5 7/8") |
|
|
|
|
|
|
|
|
| |
NOTE: |
|
|
|
| (5 7/8") |
|
|
|
| 475 mm |
|
|
| 475 mm | 35 mm |
| |
Service clearance |
| 32 mm |
|
|
| |||
|
|
|
|
|
| |||
| DIMENSIONS 500DCS |
|
|
|
|
| ||
is 760 mm (30 in.) |
| (18 3/4") | (1 1/4") |
|
| (18 3/4") | (1 3/8") |
|
|
|
| 356 mm | 200 mm |
| 356 mm | 200 mm | |
|
|
|
| (14") | ||||
|
|
| (14") |
| (8") |
| (8") | |
|
|
|
|
|
| |||
SUPPLY AIR | 1245 mm |
| 717 mm |
|
| 717 mm |
| |
FROM OUTSIDE |
|
|
|
| ||||
DEFROST | DRAIN CONNECTION (49") | SUPPLY AIR | (28 1/4 ") |
|
| (28 1/4") |
| |
FRONT VIEW | TO BUILDING | INTERIOR DUCT |
| EXTERIOR DUCT | ||||
|
| |||||||
|
|
| ||||||
|
|
| CONNECTION SIDE |
| CONNECTION SIDE |
OPTIONS
includes Programmable Time Clock, Dehumidistat and Air Sentry™
DATE: __________________________
All units conform to CSA and UL standards.
WARRANTY
Units carry a 15 year warranty on the heat recovery core and a 2 year replacement parts warranty.
| 511 McCormick Blvd. | |
PROJECT: ________________________________________ | London, Ontario N5W 4C8 | |
Ph: (519) | ||
| ||
| Fx: (519) | |
MECHANICAL CONTRACTOR: ________________________________ | Email: nutech@lifebreath.com | |
Website: www.lifebreath.com | ||
6 | ||
0011 | ||
|