Selecting the Correct Size HRV/ERV
Commercial and Institutional Requirements
For outdoor air requirements, ASHRAE has produced the Ventilation Standard
Small restaurants, Donut Shops and Fast food stores | Bank |
|
| ||
Seats | 40 |
| Customers | 25 |
|
Employees | 5 |
| Staff | 9 |
|
Total | 45 |
| Total | 34 |
|
ASHRAE requirement | 20 cfm (10L/s) per person | ASHRAE requirement | 20 cfm (10L/s) per person | ||
Ventilation required | 45 x 20 = 900 cfm (450 L/s) | Ventilation required | 34 x 20 = 680 cfm (320 L/s) |
Bar or Tavern |
|
| Bingo Hall |
|
|
Seats | 50 |
| Customers | 180 |
|
Employees | 7 |
| Staff | 20 |
|
Total | 57 |
| Total | 200 |
|
ASHRAE requirement | 30 cfm (15L/s) per person | ASHRAE requirement | 30 cfm (15L/s) per person | ||
Ventilation required | 57 x 30 = 1710 cfm (855 L/s) | Ventilation required | 200 x 30 = 6000 cfm (3000 L/s) |
Classroom and School Portables | Print Shop, Duplicating |
| ||
Seats | 29 |
| Square footage of shop | 2000 square ft (m2) |
Teacher | 1 |
|
|
|
Total | 30 |
| ASHRAE requirement | 0.5 cfm/ft2 (2.5L/s - m2) |
ASHRAE requirement | 15 cfm (7.5L/s) per person |
| per person | |
|
| |||
Ventilation required | 30 x 15 = 450 cfm (255 L/s) | Ventilation required | 2000 x 0.5 = 1000 cfm (500 L/s) |
Beauty Salon |
| Swimming Pools |
Customers | 12 | Refer to “Pool” Models Installation Manuals. |
Employees | 6 |
|
Total | 18 |
|
ASHRAE requirement | 25 cfm (12.5L/s) per person | |
Ventilation required | 18 x 25 = 450 cfm (255 L/s) |
MAKE UP HEAT REQUIREMENT at 1200 CFM (566L/s)
|
| Nominal | Nominal | Nominal |
Outdoor Temp. | kW Req. for | kW Req. for | kW Req. for | |
C° | F° | 20°C (68°F) | 25°C (77°F) | 30°C (86°F) |
|
| Air Delivery | Air Delivery | Air Delivery |
|
|
|
|
|
0 | 32 | 7 | 10 | 14 |
14 | 10 | 14 | 17 | |
12 | 15 | 19 | ||
15 | 19 | 22 | ||
17 | 21 | 24 | ||
|
|
|
|
|
5