Selecting the Correct Size HRV/ERV

Selecting the Correct Size HRV/ERV

Commercial and Institutional Requirements

For outdoor air requirements, ASHRAE has produced the Ventilation Standard 62-1989 that is used to determine acceptable ventilation rates. This standard is referenced directly or used as “Good Engineering Practice” in most Code documents or design criteria.

Small restaurants, Donut Shops and Fast food stores

Bank

 

 

Seats

40

 

Customers

25

 

Employees

5

 

Staff

9

 

Total

45

 

Total

34

 

ASHRAE requirement

20 cfm (10L/s) per person

ASHRAE requirement

20 cfm (10L/s) per person

Ventilation required

45 x 20 = 900 cfm (450 L/s)

Ventilation required

34 x 20 = 680 cfm (320 L/s)

Bar or Tavern

 

 

Bingo Hall

 

 

Seats

50

 

Customers

180

 

Employees

7

 

Staff

20

 

Total

57

 

Total

200

 

ASHRAE requirement

30 cfm (15L/s) per person

ASHRAE requirement

30 cfm (15L/s) per person

Ventilation required

57 x 30 = 1710 cfm (855 L/s)

Ventilation required

200 x 30 = 6000 cfm (3000 L/s)

Classroom and School Portables

Print Shop, Duplicating

 

Seats

29

 

Square footage of shop

2000 square ft (m2)

Teacher

1

 

 

 

Total

30

 

ASHRAE requirement

0.5 cfm/ft2 (2.5L/s - m2)

ASHRAE requirement

15 cfm (7.5L/s) per person

 

per person

 

 

Ventilation required

30 x 15 = 450 cfm (255 L/s)

Ventilation required

2000 x 0.5 = 1000 cfm (500 L/s)

Beauty Salon

 

Swimming Pools

Customers

12

Refer to “Pool” Models Installation Manuals.

Employees

6

 

Total

18

 

ASHRAE requirement

25 cfm (12.5L/s) per person

Ventilation required

18 x 25 = 450 cfm (255 L/s)

MAKE UP HEAT REQUIREMENT at 1200 CFM (566L/s)

 

 

Nominal

Nominal

Nominal

Outdoor Temp.

kW Req. for

kW Req. for

kW Req. for

20°C (68°F)

25°C (77°F)

30°C (86°F)

 

 

Air Delivery

Air Delivery

Air Delivery

 

 

 

 

 

0

32

7

10

14

-10

14

10

14

17

-20

-4

12

15

19

-30

-22

15

19

22

-40

-40

17

21

24

 

 

 

 

 

5