Air Flow Balancing

It is necessary to have balanced air flow in an HRV. The volume of air brought in from the outside must equal the volume of air exhausted by the unit. If the air flow is not properly balanced, then:

The HRV may not operate at its maximum efficiency

A negative or positive air pressure may occur in the house

The unit may not defrost properly

Failure to balance HRV properly may void warranty

CAUTION

Ensure balanced air flow in HRV. Excessive positive pressure may drive moist indoor air into the external walls of the building where it may condense (in cold weather) and degrade structural components. May also cause key holes to freeze up.

Excessive negative pressure may have several undesirable effects. In some geographic locations, soil gases such as methane and radon gas may be drawn into the home through basement/ground contact areas.

Read the Application Warning in Clearances & Requirements section of this manual!

WARNING

Ensure balanced air flow in HRV. Excessive negative pressure may also cause the back-

drafting of vented combustion equipment.

Prior to balancing, ensure that:

1.All sealing of the duct system has been completed.

2.All of the HRV’s components are in place and functioning properly.

3.Balancing dampers are fully open.

4.Unit is on HIGH speed.

5. Air flow in branch lines to specific areas of the house should be adjusted first prior to balancing the unit. A smoke pencil used at the grilles is a good indicator of each branch line's relative air flow.

6.After taking readings of both the stale air to the HRV duct and fresh air to the house duct, the duct with the lower CFM ([L/s] velocity) reading should be left alone, while the duct with the higher reading should be dampered back to match the lower reading.

7. Return unit to appropriate fan speed for normal operation

8. A field-supplied balancing damper for the stale air side is required for system balancing.

Balancing Procedure

The following is a method of field balancing an HRV using a Pitot tube, which is advantageous in situations when flow stations are not installed in the duct system. Procedure should be performed with the HRV on high speed.

The first step is to operate all mechanical systems on high speed, which have an influence on the ventilation system, i.e. the HRV itself and the air handler, if applicable. This will provide the maximum pressure that the HRV will need to overcome, and allow for a more accurate balance of the unit.

Drill a small hole in the duct (about 3/16"), three feet downstream of any elbows or bends, and one foot upstream of any elbows or bends. These are recommended distances but the actual installation may limit the amount of straight duct.

The Pitot tube should be connected to a magnehelic gauge or digital manometer capable of reading from 0 to 0.25 in. (0-62 Pa) of water, preferably to 3 digits of resolution. The tube coming out of the end of the Pitot is connected to the high pressure side of the gauge. The tube com- ing out of the branch of the Pitot is connected to the low pressure or reference side of the gauge.

Insert the Pitot tube into the duct; pointing the tip into the air flow.

For general balancing it is sufficient to move the Pitot tube around in the duct and take an average or typical reading. Repeat this procedure in the other (supply or return) duct. Determine which duct has the highest air flow (highest reading on the gauge). Then damper that air flow back to match the lower reading from the other duct. The flow should now be balanced.

Actual air flow can be determined from the gauge reading. The value read on the gauge is called the velocity pressure. The Pitot tube comes with a chart that will give the air flow velocity based on the velocity pressure indicated by the gauge. This velocity will be in either feet per minute or meters per second. To determine the actual air flow, the velocity is multi- plied by the cross sectional area of the duct being measured.

This is an example for determining the air flow in a 6" duct.

The Pitot tube reading was 0.025 inches of water.

From the chart, this is 640 feet per minute.

The 6" duct has a cross sectional area of = [3.14 x (6"÷12)2]÷4

= 0.2 square feet

The air flow is then:

640 ft./min. x 0.2 square feet = 128 cfm

For your convenience, the cross sectional area of some common round duct is listed below:

DUCT DIAM. (inches)

CROSS SECTION AREA (sq. ft.)

5

0.14

6

0.20

7

0.27

The accuracy of the air flow reading will be affected by how close to any elbows or bends the readings are taken. Accuracy can be increased by taking an average of multiple readings as outlined in the literature sup- plied with the Pitot tube.

24

Page 24
Image 24
Lifebreath RNC120F, 120ERV installation manual Air Flow Balancing, Balancing Procedure, Prior to balancing, ensure that

120ERV, RNC120F specifications

The Lifebreath RNC120F,120ERV is a highly efficient energy recovery ventilator designed to promote better indoor air quality while minimizing energy consumption. This model is ideal for a variety of residential applications, providing a cost-effective solution for ensuring a continual supply of fresh outdoor air into living spaces. The RNC120F,120ERV features advanced technologies that allow it to operate efficiently, making it a favorable choice among homeowners and building professionals alike.

One of the standout features of the RNC120F,120ERV is its energy recovery capability. This system can recover up to 85% of the energy from the outgoing stale air and transfer it to the incoming fresh air, which significantly reduces heating and cooling costs. This is particularly advantageous in regions with extreme seasonal climates, as it minimizes the demand on HVAC systems.

The unit is equipped with a high-efficiency ECM motor that operates quietly and consumes less energy compared to traditional motors. This technology not only contributes to lower energy bills but also ensures a more comfortable and peaceful indoor environment. The RNC120F,120ERV has adjustable airflow settings, allowing users to customize the level of ventilation according to their specific needs.

Another important characteristic of the Lifebreath RNC120F,120ERV is its compact design. It can easily be installed in tight spaces, making it suitable for a variety of home layouts and sizes. This versatility allows homeowners to benefit from improved air quality without sacrificing valuable living space.

The system also features a built-in filter that helps remove airborne particles, allergens, and pollutants, enhancing the overall air quality in the home. Regular maintenance and replacement of the filters are simple, ensuring that the unit continues to perform at its best.

In addition to its functional attributes, the RNC120F,120ERV is designed with durability in mind. It is constructed from high-quality materials that can withstand the rigors of continuous operation in various environments. Furthermore, the unit meets strict energy efficiency standards, making it a responsible choice for environmentally conscious consumers.

Overall, the Lifebreath RNC120F,120ERV combines energy efficiency, advanced technology, and ease of use, making it an excellent investment for anyone looking to improve their indoor air quality while keeping energy costs low.