Simplified Installation for HRV

Application Illustrations

HRV–Option 2

 

 

Simplified Installation for HRV

(Return/Return Method)

It is mandatory that the air handler blower run continuously or HRV operation be interlocked with the air handler blower.

Check local codes/authority having jurisdiction for acceptance.

(Return/Return Method) WARNING

HRV must be balanced.

DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM and

EXHAUST AIR STREAM to the AIR HANDLER COLD AIR RETURN

 

Return Air

*Unit is normally balanced on

 

 

40" (1m) MINIMUM

3’ (915 mm) min.

HIGH speed with air handler

Outdoors

recommended

blower ON.

 

Exhaust Air to Outside

 

 

Fresh Air From Outside ●Check local codes/authority having jurisdiction for acceptance.

Fresh Air to Building

Field-supplied Balancing Damper (optional)

Cool Air

Return

NOTES:

1.Air handler blower must operate when ventilation from HRV is required. The air handler should be set to run continuously or interlocked with HRV.

2.A minimum separation of 40 inches (1m) is required between the two direct connections.

3.The exhaust air connection should be upstream of the supply air connection to prevent exhausting any fresh air.

4.Weather hood arrangement is for drawing purposes only. Six feet (2m) minimum separation required. 18" inches (460mm) above grade minimum or above anticipated snow level.

5.Due to the differences in pressure between the HRV and the equipment it is being connected to, the HRV's air flow must be confirmed on site, using the balancing procedure found in the installation manual.

Air

Handler

High efficiency filter

or electronic air cleaner

DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM and WARNING

Defrost air port needs to be drawn from clean area without combustion appliances. To avoid backdrafting of combustion products, never draw defrost air from a room with a naturally aspirated appliance, i.e. furnace, hot water heater, gas dryer, stove, fire place etc.

EXHAUST AIR STREAM to the AIR HANDLER COLD AIR RETURN CAUTION

Weather hood arrangement - requires a minimum of 6' (2m) separation and a minimum of 18" (460mm) clearance above grade or anticipated snow level.