Engineering Data | Model RNC120F |
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The
MOTORS AND BLOWERS
Each Air stream has an independent motorized impeller. 3 speed operation 120VAC
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.
DEFROST
Fan defrost system. Fresh air motor turns off and Exhaust motor switches to high speed to defrost core.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connection 1 - 1/2" (12 mm) OD.
CONTROLS
Unit is supplied with a remote HRV control box which can be conveniently located within
HRV System Control
HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by connecting remote controls to designated terminals inside electrical box of HRV.
Standard LOW SPEED SETTING can be increased to medium low.
Off (Standby)/Low or OFF/HIGH speed operation is also available.
DUCT CONNECTIONS
5” duct connections with “field” selectable standard airflow or reverse airflow for limited room installations.
WEIGHT 42 lbs. (19 kg)
SHIPPING WEIGHT 45 lbs. (20.5 kg)
OPTIONAL ACCESSORIES
WARRANTY
Units carry a lifetime warranty on the heat recovery core and a five year replacement parts warranty.
TOP VIEW |
|
EXHAUST | FRESH AIR |
TO BUILDING | |
AIR FROM |
|
BUILDING |
|
18” | All Duct Collars are |
FRESH AIR | 5" diameter (127 mm) |
| |
FROM | EXHAUST AIR |
OUTSIDE | |
| TO OUTSIDE |
9” |
|
19” | SERVICE CLEARANCE FROM |
BOTTOM OF UNIT IS MINIMUM 3'0" |
Performance
Net supply air flow in cfm (L/s) against external static pressure
E.S.P |
|
|
|
(external static pressure) |
| [cfm (L/s)] | |
@ 0.1" (25 Pa) |
| 125 | (59) |
@ 0.2" (50 Pa) |
| 120 | (56) |
@ 0.3" (75 Pa) |
| 114 | (54) |
@ 0.4" (100 Pa) |
| 109 | (51) |
@ 0.5" (125 Pa) |
| 106 | (50) |
@ 0.6" (150 Pa) |
| 99 | (47) |
@ 0.7" (175 Pa) |
| 94 | (44) |
@ 0.8" (200 Pa) |
| 89 | (42) |
|
|
|
|
Sensible Effectiveness |
|
|
|
@ 65 cfm (30 L/s) | 32°F (0°C) | 72% | |
*Sensible Efficiency |
|
|
|
@ 65 cfm (30 L/s) | 32°F (0°C) | 55% | |
*Sensible Efficiency |
|
|
|
@ 65 cfm (30 L/s) | 45% | ||
VAC @ 60HZ |
|
| 120 |
WATTS / Low speed. |
|
| 63 |
|
|
|
|
WATTS / High speed |
|
| 150 |
|
|
|
|
Amp rating |
|
| 1.5 |
*Sensible Efficiency - thermal **Latent Efficiency - moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency - takes into account all power inputs
| 140 |
|
|
|
|
|
| 3 - High Speed |
| |
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| 2 - Medium Low Speed |
| |
| 120 | 3 |
|
|
|
|
| 1 - Low speed |
|
|
|
|
|
|
|
|
|
|
|
| |
| 100 |
|
|
|
|
|
|
|
|
|
(cfm) |
|
|
|
|
|
|
|
|
|
|
Flow | 80 | 2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Air |
| 1 |
|
|
|
|
|
|
|
|
| 60 |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
| 40 |
|
|
|
|
|
|
|
|
|
| 20 |
|
|
|
|
|
|
|
|
|
| 0 | 0.1 | 0.2 | 0.3 | 0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 |
Static Pressure (in w.g.)
All units conform to CSA and UL standards.
Date: ______________________________________________ | Contractor: __________________________________________ |
Tag: ________________________ Qty: __________________ | Supplier: ____________________________________________ |
Project: _____________________________________________ | Quote#: ____________________________________________ |
Engineer: ___________________________________________ | Submitted by: ________________________________________ |
2