Lifebreath 120ERV Dehumidistat Operation HRV only, Defrost Operation, Factory Setting, Option

Models: 120ERV RNC120F

1 28
Download 28 pages 11.22 Kb
Page 23
Image 23
Dehumidistat Operation (HRV only)

Dehumidistat Operation (HRV only)

The optional HRV remote controls include a dehumidistat which controls humidity levels during the heating season. The control has a selector knob with set points ranging from 20% to 80% relative humidity (RH). Most people are comfortable when indoor relative humidity levels are in a range from 30 to 45%.

The dehumidistat switches the ventilator to high speed when the moisture level in the building exceeds the desired setpoint. The dehumidistat switches the HRV back to low speed ventilation when the humidity has been reduced below the setpoint. The dehumidistat should only be used during the heating season. It must be set to OFF position throughout the rest of the year.

Defrost Operation

The fan defrost HRV is equipped with an electronically controlled fan defrost system to remove frost that collects on the warm air side of the aluminum heat transfer sur- faces of the heat exchanger core. When the outside air temperature drops below 27°F (3°C), defrost is activated which provides for an automatic defrost cycle. During the automatic defrost cycle, the fresh air supply is shut off while the exhaust fan continues to operate. This allows the warm inside air to flow through the heat exchanger core melting frost accumulation. After the defrost period, the

fresh air supply fan returns to the normal speed and fresh outside air continues to be drawn into the building. Water from the melted frost collects in the bottom of the drip pans and drains out through the bottom drain connections. The defrost cycle repeats automatically until the air tem- perature rises above 27°F (-3°C).

Defrost Cycle DIP Switch Settings

Defrost DIP Switch Settings (located on the circuit board) can be adjusted to increase the unit’s run (ventilation) time. The three minute defrost time cannot change.

Factory Setting

 

Option 1*

 

Option 2*

3 minute defrost time

3 minute defrost time

3 minute defrost time

17 minute run time

25 minute run time

30 minute run time

 

 

ON

 

 

ON

 

 

ON

 

 

 

 

HS

REMOTE

DFR2

DFR3

HS

REMOTE

DFR2

OFF DFR3

 

HS

 

REMOTE

 

DFR2

ON

DFR3

Defrost Operation OFF

Defrost Cycle DIP Switch SettingsFactory Setting ON

SW1

SW1

SW1

*Lengthening the run time may result in ice build-up on the core.

23

Page 23
Image 23
Lifebreath 120ERV Dehumidistat Operation HRV only, Defrost Operation, Defrost Cycle DIP Switch Settings, Factory Setting