Interlocking HRV Operation to an Airhandler/Furnace Blower

Interlocking HRV Operation to an Airhandler/Furnace Blower

When using the Interface relay contacts to initiate blower operation on a fur- nace, certain thermostats will initiate the outdoor cooling condenser when R and G are closed.

Use this wiring configuration to prevent the Interface relay contacts from initializing the condenser unit. This problem can occur at the thermostat because the Y termi- nal is connected to the G terminal internal to the stat. When R and G are closed at the furnace (by dehumidistat or relay) 24 Volts is sent to G at thermostat. 24 Volts is then sent through Y which will initiate outdoor condenser.

22

Page 22
Image 22
Lifebreath RNC120F, 120ERV installation manual Interlocking HRV Operation to an Airhandler/Furnace Blower