|
| valves, the valve should open. Check for gas |
|
| pressure at the manifold tap located just before |
|
| the burner. If there is no pressure, check the |
|
| incoming gas supply to be sure all manual valves |
|
| are open and flexible gas hose is properly |
|
| connected. If gas is present, and the gas control |
|
| valve is energized, but there is no gas pressure at |
|
| the burner manifold, replace the gas control |
|
| valves. |
Flame will not stay lit | Hot surface igniter | Six seconds after the gas valve opens, ignition |
|
| must occur. If flame is not detected, the ignition |
|
| control will shut off and lock out. To reset the |
|
| ignition control, turn off the power switch for 45 |
|
| seconds, then turn the switch on to |
|
| The ignition control requires a minimum of 0.8 DC |
|
| microamps to prove flame. To check flame |
|
| sensing operation, connect a digital multimeter |
|
| (capable of measuring DC microamps) between |
|
| the “ground” terminal on ignition control and the |
|
| ground lead. |
|
| NOTE: This is a current measurement and the |
|
| meter must be connected in series |
|
| If these readings are not achieved, replace hot |
|
| surface igniter. |
|
| NOTE: The DC microamp test must be conducted |
|
| with the oven in low flame (bypass) operation. Set |
|
| the temperature control to the lowest setting. |
| Power supply | If there is sufficient microamp current, but the |
|
| flame will not stay lit, check for proper polarity of |
|
| the 120VAC power supply. |
| Ignition control | If there is sufficient microamp current, and the |
|
| 120VAC polarity is correct, but the flame will not |
|
| stay lit, replace the ignition control. |
|
| NOTE: Check for proper ground connection on |
|
| ignition control. |
| NOTE: Flame should be on at |
|
| this time |
|
|
|
|
Low flame is on, | Control transformer | Check for 120VAC supply to the primary of the |
but no main flame |
| control transformer. If no voltage is present, trace |
|
| wiring back to the main power switch. If voltage is |
|
| present, check for 24VAC at the transformer |
|
| secondary. If there is primary voltage, but no |
|
| secondary voltage, replace the control |
|
| transformer. |
| Oven control | Check for 24VAC supply to control. If no voltage is |
|
| present, trace wiring back to control transformer. If |
|
| 24VAC is present, check for a |
|
| display. If there is 24VAC supplied, but there is no |
|
|
|
|
| control. |
|
| If there is a |
|
| to maximum temperature (see installation |
|
| operations manual for temperature adjustment). |
|
| With the control set at maximum temperature, |
|
| check for 120VAC at the temperature regulation |
|
| valve. If there is voltage at the temperature |
|
| regulation valve, proceed to “Temperature |
|
| regulation valve” for next check. If there is no |
|
| voltage at the temperature regulation valve, trace |
|
| wiring back to the oven control. If there is no |
Impinger II – Advantage Digital Service Manual - Domestic | 9 |