| Check for voltage on both sides of the switch. Terminals are | |
| control box | normally closed. If open, reset and test oven for proper |
|
| operation. If thermostat will not hold, and control box |
|
| temperature is not exceeding 140°F (60°C), replace thermostat |
| Relay, oven power | Check for 120 VAC to the relay coil. If voltage is not present, |
|
| Trace wiring back to the |
|
| check to insure contacts are closing. Check for 120 VAC |
|
| supplied to terminal #2 of the relay. If voltage is not present at |
|
| terminal #2, trace wiring back to the 10 Amp fuse. Replace relay |
|
| as needed. |
| Control transformer | Check for 120 VAC supply to the primary of the control |
|
| transformer. If no voltage is present, trace wiring back to the |
|
| oven power relay. If voltage is present, check for 24 VAC at the |
|
| transformer secondary. If there is primary voltage but no |
|
| secondary voltage, replace control transformer. |
| Conveyor motor | Check for 120 VAC supply to the conveyor motor at wire #14 to |
|
| neutral. If no voltage is present, trace wiring back to the primary |
|
| of the control transformer. If voltage is present and the motor will |
|
| not run, check the motor windings for opens or shorts. |
|
| WITH POWER OFF: Check the motor windings as follows: |
|
| Grey to black - 38Ω approx. |
|
| Grey to blue - 38Ω approx. |
|
| Blue to black - 75Ω approx. |
|
| If any of the above fails, replace conveyor motor. |
| Capacitor, conveyor | Check for shorts or grounds. Replace capacitor as needed. |
| motor | WARNING: Capacitor has a stored charge, discharge before |
|
| testing. |
| Switch, conveyor | Check continuity between switch terminals. Replace switch as |
| reversing | needed. |
| Oven control | If there is 120VAC supplied to the motor, and the motor, |
|
| capacitor, and reversing switch check good, replace the oven |
|
| control. |
Conveyor motor runs, | NOTE: Display will |
|
but there is no speed | indicate “Belt Jam” |
|
display |
|
|
| Oven control | Check for output voltage from oven control to hall effect sensor |
|
| (sensor is located in conveyor motor). Measure voltage at the |
|
| motor connector, red wire and yellow wire. Voltage should be |
|
| approx. 10VDC. If no voltage is present, trace wiring back to |
|
| oven control. If there is no voltage present at the oven control, |
|
| replace the oven control. |
| Conveyor motor | If there is voltage supplied to the hall effect sensor, check for a |
|
| frequency output from the hall effect sensor. Measure frequency |
|
| across the yellow and white wires at the motor connector. |
|
| Frequency reading should be approx. 25 – 100 Hz. If these |
|
| readings are not achieved, replace conveyor motor. If the |
|
| readings are achieved, proceed. |
| Oven control | If the hall effect sensor readings are correct, but there is no |
|
| speed indicated on the display, replace the oven control. |
8 | Low Profile – 1600 Series Advantage Digital Service Manual – Domestic |