INSTALLATION |
REMOTE CONTROL
OUTPUT
The Vantage is equipped with a
When in TOUCH START TIG mode and when a Amptrol is connected to the
The
WARNING
NOTE: When a wire feeder with a built in welding voltage control is connected to the
AUXILIARY POWER RECEPTACLES
The auxiliary power capacity of the Vantage is 12kVA of 50Hz three phase power. All models are protected by an RCD (Residual Current Device) and a 3 phase 20 amp circuit breaker. The auxiliary power capacity in watts equivalent to
This model has:
1 x 3 phase and neutral Residual Current Device (RCD) protection (30mA)
1 x 3 phase 20 amp Circuit Breaker
1 x 3 phase 380 volt 18.5 amp
3 x 1 phase 15 amp Circuit Breakers
3 x 1 phase 220 volt 15 amp per outlet
Note: The
The auxiliary power receptacles should only be used with three or four wire earthed type plugs or approved double insulated tools. The current rating of any plug used with the system must be at least equal to the current capacity of the associated receptacle.
STANDBY POWER CONNECTIONS
The Vantage is suitable for temporary, standby or emergency power using the engine manufacturer’s recommended maintenance schedule.
The Vantage can be permanently installed as a standby power unit for 380/220 volt (50Hz). Connections must be made by a licensed electrician who can determine how the 380/220 VAC power can be adapted to the particular installation and comply with all applicable electrical codes. The following information can be used as a guide by the electrician for most applications.
1.Install an isolation switch between the power company meter and the premises disconnect. (the Vantage and the power company supplies must not be connected together).
Switch rating must be the same or greater than the customer’s premises disconnect and service over current protection.
2.Take necessary steps to assure load is limited to the capacity of the Vantage by installing a 20 amp, 380 VAC three pole circuit breaker. Loading above the rated output will reduce output voltage below the allowable
3.Install a 20 amp 3 phase plug to the
4.Plug this cable into the 3 phase receptacle on the Vantage case front.
Vantage 575